Configuration and CFG-300 LCD Service Tool
36
Command Menu/Panel Config/Features/
3.Output Circuit Correlation
[X] DISABLE->Default
[ ] ENABLE
If disabled, whatever correlation
is set in the correlation section
is effective. If enabled, all the
output circuits are correlated to
all the input circuits.
Command MenuPanel Config/Features/
4.Waterflow/Sprinkler Retard
Operation
[X] DISABL ->Default
[ ] ENABLE
If disabled, all the initiating
circuits configured as water flow
or sprinkler act as non-verified
alarms. If enabled, retard
operation is performed for
initiating circuits configured as
water flow or sprinkler.
(See Water flow Alarm and
Sprinkler Alarm description)
Command Menu/Panel Config/Features/
5.Aux. disconnect, disconnects
Aux Alarm relay and all correlated
relays
[ ] ENABLE
[X] DISABLE->Default
In the default mode this function
will disconnect the Auxiliary
Alarm Relay when selected by
the Aux Disconnect button.
If enabled, this function will
disconnect the Auxiliary Alarm
Relay and all correlated relays
by pressing the Aux Disconnect
button.
Correlated relays
include: RM-306 relays, SRM-
312 relays.
Command Menu/Panel Config/Features/
6.Signal-Silence Inhibit timer
[X] DISABLE->Default
[ ] 10 SEC
[ ] 20 SEC
[ ] 30 SEC
[ ] 1 MIN
Use this function to inhibit the
“SIGNAL SILENCE” switch for a
desired length of time. This time
period should expire before the
signals may be silenced.
According to the Canadian
National Building Code, this
timer should be set to one
minute.
Command Menu/Panel Config/Features/
7. Aux. disconnect, disconnects
common alarm relay and common
supervisory relay
[ ] ENABLE
[X] DISABLE->Default
If enabled, this function will
disconnect (when the Aux.
disconnect switch is pressed)
the Common Alarm relay and
Common Supervisory relay and
the PR-300 will not transmit a
supervisory or alarm event.
If disabled, the Aux disconnect
switch has no effect on the
Common Alarm relay, the
Common Supervisory relay and
the PR-300.
Command Menu/Panel Config/Features/
8.Auto Signal Silence Timer
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 15 Min
[ ] 20 Min
[ ] 30 Min
Use this function to determine
the time period for which the
indicating circuits will sound
before they are automatically
silenced. According to the
Canadian National Building
Code, this timer should not be
set to less than 20 minutes.
O p t . C k t . C o r r .
[ X ] D I S A B L E
W a t e r f l o w / S p r k . R e t d
[ X ] D I S A B L E
A u x D i s C o r r
[ X ] D I S A B L E
S i g - S i l . I n h i b i t T m r
[ X ] D I S A B L E
A u x D i s , D i s A l m & S p v
[ X ] D I S A B L E
A u t o S i g - S i l . T i m e r
[ X ] D I S A B L E