FA-300-6L Installation and Operation Manual
7
Mechanical Installation
Installing the Enclosure
Install the FA-300 Series Fire Alarm Panel enclosure as shown below. Mount enclosure surface mount using the
four mounting holes, as shown and the screws provided.
Figure 1: Box dimensions, surface mount
Remove the door (also disconnect the ground strap), the dead front and semi-flush mount the backbox into the wall. Peel the adhesive cover
from the trim ring and stick to the wall surface around the backbox, after wall is finished.
The figure below shows a cross-section of the semi-flush mounted backbox and the trim ring. Make sure to
allow a minimum depth of 1”
above the wall surface
for proper door opening.
17"
22.5"
Adhere trim ring to
wall surface around
the FA-300 backbox.
PLACE FA-300TRB TRIM RING OVER BACKBOX
14.5"
4.
5"
11"
20.0"
1.5"
5.425"
14.5"
3.5"
1"
3.5" is the maximum depth
for semi-flush mounting
using the flush trim ring
1" is the minimum depth
above the wall required
for semi-flush mounting
4 Mounting
Holes for
Surface
Mounting
TRIM RING
MIN 1”
WALL
WOOD OR
METAL STUD
BACKBOX