Appendix C: Specifications
FA-300-6L series fire alarm control panel
RM-306 adder module
Digital Signal Processor (DSP) based design. Fully configurable
using CFG-300 with Password Access.
Electrical Ratings
AC line voltage
120VAC, 60Hz, 1.7A / 240VAC, 50Hz, 0.85A,10A slow blow fuse
on secondary of transformer
Power Supply Rating
6.35 amps maximum at secondary of transformer
Battery
Type:
24VDC Gel-Cell/Sealed lead acid - 10AH to 24AH
Charging capability:
10AH to 24AH
Protection:
10A
on board (F1) slow blow micro fuse
Indicating circuits
4 supervised style Y (Class B) indicating circuits, configured as
strobes or audibles. Terminals are labeled “SIG 1,2,3,4”
Power limited / Regulated 24VDC FWR / 1.7A @ 49C per circuit
Max power allowed = 5A
- 1.7A (aux power unfiltered if used)
- 0.5A (aux power filtered if used)
- 0.3A (4-wire smoke power if used)
if no auxiliaries are used the max power is 5A for the indicating
circuits
Current consumption
Standby 123mA/Alarm 316mA
Aux supply (non resettable)
power limited / 21.1Vdc regulated / 500mA max
4-wire smoke supply (resettable)
Power limited/21.1VDC regulated / 300mA max
Unfiltered supply (full wave rectified)
Power limited / Regulated 24VDC FWR / 1.7A max at 49C
Auxiliary Relays (Common alarm/supv/trb/ and
auxiliary second alarm)
Must be connected to a listed power-limited source of supply
FormC / 28VDC / 1A resistive load max.
Only suitable for DC applications such as visual indicators.
Initiating circuit
6 supervised style B (Class B) initiating circuits, configurable
(normal or verified). Terminals are labeled “DET”. Compatibility
ID “A”
Power limited / 19VDC reg. / 3mA for detectors / 200mV AC
ripple / 45mA max (alarm short)
1 RS-485 Connection
For remote annunciators. Terminals are labeled “RS-485”.
PR-300 Polarity reversal city tie module (optional)
RM-306 Relay Module (optional)
Must be connected to a listed power-limited source of supply
Contact rating
NO / NC / 28VDC per contact / 1A resistive load
max.
Only suitable for DC applications such as visual indicators.
Current consumption
standby 0mA, alarm 80mA
RM-306 Input Class A Converter module
Standby 0mA / alarm 0mA
RM-306 Output Class A Converter module
Standby 0mA / alarm 0mA
SRM-312 Smart Relay Module
Must be connected to a listed power-limited source of supply
Contact rating
NO/NC / 28VDC per contact / 1A resistive load
max
Current consumption
standby 30mA / alarm 140mA
RAM-208/216 8/16 Zone Remote Annunciator
Standby 35mA / alarm 90mA
Remote Trouble Indicator
Standby 35mA / alarm 35mA
Polarity reversal and city tie module
City tie
power limited / 24VDC unfiltered / 250mA max / 14Ohms
trip coil
Polarity reversal
power limited / 24VDC open / 12VDC at 3.5mA /
8.5mA max (shorted)
Polarity reversal supv terminal
24VDC (normal) / -24VDC (supervisory) / 0V (trouble)
Polarity reversal alarm terminal
24VDC (normal) / -24VDC (alarm) / 0V (trouble)
Current consumption
standby 50mA / alarm 300mA (city tie in
use) / alarm 70mA (city tie not in use)
Ground Fault circuit
Less the 3K will generate a ground fault.
System Model:
FA-300-6L Series LED Version Fire Alarm Control Panel
System Type:
Local Auxiliary (using PR-300), Remote Protected Premises Station (using PR-300 or
FA-300-6LD). Central Station Protected Premises (using FA-300-6LD)
Type of Service:
A, M, WF, SS
Type of Signalling
: Non-Coded
Applicable Standards:
NFPA 70 and 72, UL-864 Rev. 9, ULC S-524, ULC S-527-99, ULC-S-536