Wiring Tables and Information
Table 3: Initiating Circuit Wiring
Table 4: Indicating Circuit Wiring
Four-Wire Smoke Power (regulated)
4-wire smoke power is provided for 4-wire smoke detectors. This filtered supply is supervised therefore a short will
disconnect the power through the relay until the “RESET” key is pressed. A trouble signal will be generated once
there is a short. This supply is rated at 22.3VDC regulated/300mA max/1V voltage drop maximum.
Supervised Auxiliary Power (regulated)
Supervised auxiliary power is used to power the remote annunciators and smart relay modules. This filtered circuit
is supervised therefore a short will disconnect the power through the relay until the “RESET” key is pressed. A
trouble signal will be generated once there is a short.This supply is rated at 22.3VDC regulated/500mA max/1V
voltage drop maximum.
Auxiliary Power (unfiltered)
This unfiltered supply is not supervised. This supply is rated at 24VDC FWR/1.7A max. If there is a short on this
circuit, the auxiliary power does not recover automatically when the short is removed. The main power must be
disconnected, then reconnected and the panel reset to re-establish the auxiliary power supply.
Wire gauge
Maximum wiring run to last device
AWG
Feet
Meters
22
2990
910
20
4760
1450
18
7560
2300
16
12000
3600
14
19000
5800
12
30400
9200
Total
signal
load in
amperes
Maximum wiring run to last device
Max. loop
resistance
in ohms
18 AWG
16 AWG
14 AWG
12 AWG
Feet
Meters
Feet
Meters
Feet
Meters
Feet
Meters
0.06
2350
716
3750
1143
6000
1829
8500
2591
30
0.12
1180
360
1850
567
3000
915
4250
1296
15
0.30
470
143
750
229
1200
366
1900
579
6
0.60
235
71
375
114
600
183
850
259
3
0.90
156
47
250
76
400
122
570
174
2
1.20
118
36
185
56
300
91
425
129
1.5
1.50
94
29
150
46
240
73
343
105
1.2
1.70
78
24
125
38
200
61
285
87
1.0
Notes:
• For Class A wiring the resistance in ohms is multiplied by two.
• Maximum voltage drop should not exceed 1.8 volts.
Notes:
• For Class A the maximum
wiring run to the last device is
divided by two.
• Maximum loop resistance
should not exceed 100 ohms.
• Maximum capacitance of
0.5uF total on each initiating
circuit.