FA-300-6L Installation and Operation Manual
53
Command Menu-->Dialer-Config
Time Parameters
Command Menu/Dialer-Config/Report
Options
5.Dialer operation mode
[X] (U)DACT ->Default
[ ] DACT
Use this function to select the
functionality of the dialer. In
DACT mode only common
trouble/alarm/supervisory are
reported while in UDACT mode
all point information is reported
Note:
Refer to
How to Use the Keypad to Program the FA-300
on page 34 for detailed instructions on
making menu selections.
Command Menu/Dialer-Config/Time
Parameter
1.AC Loss delay
0 ->Default
Use this function to delay the
reporting of AC loss trouble on
the dialer for the programmed
time period.
Command Menu/Dialer-Config/Time
Parameter
2.Cellular report date
0 ->Default
Use this function to set the test
report date for the cell phone
setup. If the date is set to 0,
this means there is no test
reporting for cell phone or the
phone line is a regular line.
Other settings could be
anywhere from 01-28,
representing which day of the
month the test should be
performed. When a cell phone
service is employed for the
panel, it should only be
connected to telephone line #2
CO interface. Also, the dial
tone detection feature of Line
#2 should be disabled for cell
phone application.
Command Menu/Dialer-Config/Time
Parameter
3. Auto test time
00:30 ->Default
Use this function to set the
time for auto test. This test has
to be performed once a day to
send the test report to the
monitoring station. The time is
in 24hr format, which means
00:30 is 30 minutes after mid-
night.
Please do not use the
following test times: 00:00,
01:55, 02:00 and 03:00.
D ia le r O p e r. M o d e
[X ] ( U )D A C T
[ ] D A C T
1 A C - L o s s D e l a y
2 C e l l p h o n e D a t e
3 A u t o - T e s t T i m e
- T i m e P a r a m e t e r -
A C - L o s s D e l a y ( H r s )
0
C e l l u l a r R e p o r t D a t e
0
Auto-Test (HH:MM):
00:30