FA-300-6L Installation and Operation Manual
37
Command Menu/Panel Config/Features/
9. Number of Remote
Annunciators or smart relays
[X] NONE->Default
[ ] 1
[ ] 2
[ ] 3
[ ] 4
[ ] 5
[ ] 6
Use this function to program the
number of remote annunciators.
Any combination of remote
annunciators or smart relays
can be used as long as the
number does not exceed 6. The
annunciators’ addresses should
be linear: without gaps and in
sequence.
Command Menu/Panel Config/Features/
10.Silence Alarm transmit
[X] DISABLE->Default
[ ] ENABLE
Use this function to allow the
alarm transmits and auxiliary
alarm relay to reset on “SIGNAL
SILENCE” rather than the
“RESET” switch.
Command Menu/Panel Config/Features/
11.AC power fail delay timer
[X] NONE ->Default
[ ] 1 HRS
[ ] 2 HRS
[ ] 3 HRS
Use this function to place a
timed delay on reporting the AC
power fail trouble externally via
common trouble relay. If this
problem corrects itself within the
specified time, the common
trouble relay will not be
activated If disabled, the trouble
relay is activated immediately.
Command Menu/Panel Config/Features/
12.Common Supervisory Relay
[ ] ENABLE
[X] DISABLE ->Default
If enabled, the common
supervisory relay can be used
as common alarm relay. It will
act the same way as a common
alarm relay. If disabled, it is
used a common supervisory
relay.
Command Menu/Panel Config/Features/
13.Signal Isolators
[ ] ENABLE
[X] DISABLE->Default
Enable this function only when
suite isolators are used (Canada
only)
Command MenuPanel Config/Features/
14.Strobe Type
[X] NORMAL ->Default
[ ] MIRCOM
[ ] FARADY
[ ] WHEELOCK
[ ] GENTEX
[ ] SYSTEM SENSOR
Use this function to select the
manufacturer of the strobes
used in the system. The
selection is system-wide and
applies to all indicating circuits
configured as strobes. For
“NORMAL” strobes there is no
synchronization, while other
strobes are synchronized and
use manufacturer’s protocol to
synchronize the strobes.
Command Menu/Panel Config/Features/
15.Evacuation Code
[X] TEMPORAL->Default
[ ] CONTINOUS
[ ] MARCH TIME
[ ] CALIFORNIA
Use this function to set the rate
at which the indicating circuits
will sound.
N o . o f R e m o t e A n n u n .
[ X ] N O N E
A l m . X m i t - S i l .
[ X ] D I S A B L E
A C P w r F a i l D l y T m r .
[ X ] N O N E
C o m m o n S u p v . R e l a y
[ X ] D I S A B L E
S i g - S i l . I s o l a t o r
[ X ] D I S A B L E
S t r o b e T y p e
[ X ] N O R M A L
E v a c u a t i o n C o d e
[ X ] T E M P O R A L