OM-257 675 Page 19
5-7. Electrical Service Guide
Elec Serv 2014
−
01
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
NOTICE
−
INCORRECT INPUT POWER can damage this welding power source. This welding power source requires a CONTINUOUS supply of
input power at rated frequency
(+
10%) and voltage
(+
10%). Phase to ground voltage shall not 10% of rated input voltage. Do not use a
generator with automatic idle device (that idles engine when no load is sensed) to supply input power to this welding power source.
.
Actual input voltage should not exceed
10% of indicated required input voltage. If actual input voltage is outside of this range, output may not
be available.
60 Hz Three Phase
Input Voltage (V)
208
230
380
400
460
575
Input Amperes (A) At Rated Output
54
49
28
29
24
19
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
60
60
35
35
30
25
Normal Operating Fuses
3
80
70
45
45
35
30
Min Input Conductor Size In AWG
4
6
8
8
10
10
12
Max Recommended Input Conductor Length In Feet (Meters)
133
(41)
104
(32)
283
(86)
205
(63)
272
(83)
256
(78)
Min Grounding Conductor Size In AWG
4
8
8
10
10
10
12
Reference: 2014 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
5-8. Environmental Specifications
A. IP Rating
IP Rating
IP21S
This equipment is designed for indoor use and is not intended to be used or stored outside.
Notes
Summary of Contents for Auto-Axcess E Digital
Page 6: ......
Page 16: ...OM 257 675 Page 10...
Page 18: ...OM 257 675 Page 12 Notes...
Page 22: ...OM 257 675 Page 16 Notes...
Page 26: ...OM 257 675 Page 20 Notes...
Page 30: ...OM 257 675 Page 24 Notes...
Page 37: ...General OM 257 675 Page 31 Notes...
Page 98: ...Safety OM 257 675 Page 92 Notes...
Page 115: ...Trouble OM 257 675 Page 109 Notes...
Page 121: ...Circuits OM 257 675 Page 115 257 679 A Part 2 Of 2...
Page 123: ...Circuits OM 257 675 Page 117 257 678 A Part 1 Of 2...
Page 125: ...Circuits OM 257 675 Page 119 257 678 A Part 2 Of 2...
Page 127: ...Circuits OM 257 675 Page 121 257 676 A Part 1 Of 2...
Page 129: ...Circuits OM 257 675 Page 123 257 676 A Part 2 Of 2...
Page 130: ...OM 257 675 Page 124 Figure 15 7 Circuit Diagram For Axcess E Digital Module...
Page 131: ...Circuits OM 257 675 Page 125 257 680 A...
Page 132: ...OM 257 675 Page 126 Figure 15 8 Circuit Diagram For Motor And Digital I O Interface...
Page 133: ...Circuits OM 257 675 Page 127 258 246 A...
Page 143: ...E450 Parts OM 257 675 Page 137 Notes...