Chapter 8 Installation
Note:
Practical example:
GSM level
Position
-67dBm
Reference measurement outside the shaft
-103 dBm
Measurement at a depth of 1.20 m
-95dBm
Vertically on the edge of the shaft at a depth of approx. 15 cm
-83dBm
Centre of the shaft, horizontal on the steel fitting
-89dBm
Antenna turned by 90°
-78dBm
Centre of the shaft, vertical
-75dBm
Plastic pipe used instead of steel fitting
8.3.2.1.2 Possibilities for improving the signal quality
l
Drill a duct for the connection cable of the antenna into the concrete ring on the shaft to avoid the steel
cover
l
Insert the connection cable of the antenna in an existing ventilation or supply pipe
l
Use special types of antennas
8.3.2.1.3 Procedure for determining the optimum position of the antenna
1. Install the myDatalogGauge 3G as described in chapter "Installing the myDatalogGauge 3G " on page
50. During this process, also observe the notes regarding the influences on the signal quality (see
"Typical influences on the signal quality" on page 62).
2. Activate setup mode (see "Setup mode" on page 41).
3. Wait until it is indicated in the list of sites/applications that the device is in setup mode. This is indicated
by a speech bubble with the "Setup" inscription.
Setup mode active
4. Either wait until the speech bubble is hidden again (setup mode completed successfully) or until the
background colour of the speech bubble changes from white to red (problem detected). In both cases,
this can take up to 8min. .
Setup mode completed successfully
Problem detected
5. Open the site settings (see "Site configuration" on page 79) and click on "Setup data" to display the
GSM level determined during setup mode.
Rev. 01
63
Summary of Contents for myDatalogGauge 3G
Page 2: ......
Page 10: ...2 2 BLE Gauge 10 Rev 01 ...
Page 11: ...Chapter 2 Declaration of conformity Rev 01 11 ...
Page 12: ......
Page 13: ...Chapter 3 Ex certification Chapter 3 Ex certification 3 1 BLE 3G Gateway ATEX Rev 01 13 ...
Page 14: ...14 Rev 01 ...
Page 15: ...Chapter 3 Ex certification Rev 01 15 ...
Page 16: ...16 Rev 01 ...
Page 17: ...Chapter 3 Ex certification 3 2 BLE Gauge Rev 01 17 ...
Page 18: ...18 Rev 01 ...
Page 19: ...Chapter 3 Ex certification Rev 01 19 ...
Page 20: ...20 Rev 01 ...
Page 134: ......
Page 140: ......
Page 152: ......
Page 154: ......