9. Troubleshooting
ThermSelect®
74/100
Troubleshooting
Fault
Cause
Remedy
Defect on input
side (LP fault)
Ventilator(s) is/are not running
Check fuse, check relay
Check control signal 0-10 V
Heat source pump not running
Check fuse, relay and pump
Condenser dirty/iced over
Clean condenser, initiate thawing;
check temperatures on condenser
Expansion valve incorrectly set / defective
Request factory service
Refrigerant circulation interrupted (shut-off
valve closed, filter dryer dirty).
Request factory service
Water inside the refrigerant circulation (hu-
midity indicator in the refrigerant sight glass
yellow/red)
Request factory service
Temperature of the heat source too low
-15°C application limit reached
Water in the condenser too cold (below
20 °C)
Pre-heat heating water electric heating insert
Quick temperature change in the condenser Check volume flow
Low refrigerant level (see sight glass)
Request factory service
Controller parameter set incorrectly
Set parameters according to guide
Contact interrupted
Check LP switch wiring
Manual unlocking necessary if the low pres-
sure monitor triggers.
Defect on input
side (HD fault)
Heating pump is not running
Check fuse;
check relay/ contactor K4;
Check running wheel for dirt build-up
Water circulation interrupted or insufficient
(possibly not enough heating circuits open)
Check water circulation in heating system;
open radiator valves or positioning drives
Heating water temperature too high
No heat discharge, e.g. heat exchanger in
the boiler of the service water heater is too
small
Check technical specifications for service wa-
ter heater, min. heat exchanger surface
0.2m²/kW heat output
Air in water circulation
Vent the water circulation
Dirt catcher clogged
Clean dirt catcher
Circulation pump defective or wrong rotation
direction
Check circulation pump and rotate/replace, if
necessary
Controller parameter set incorrectly.
Set parameters according to guide
Manual unlocking may possibly be neces-
sary if the high pressure monitor triggers.
Summary of Contents for ThermSelect
Page 1: ...ThermSelect As of 9 March 2011...
Page 22: ...5 Technical Data ThermSelect 22 100 5 2 Identification plate Fig 4 Sample identification plate...
Page 25: ...ThermSelect 5 Technical Data 25 100...
Page 31: ...ThermSelect 5 Technical Data 31 100...
Page 45: ...ThermSelect 6 Assembly 45 100 Fig 10 Sensor cable heat source inlet 5...
Page 72: ...8 Maintenance ThermSelect 72 100 8 4 Spare part drawing and legend Fig 37...
Page 96: ...Your notes ThermSelect 96 100...
Page 97: ...ThermSelect Your Notes 97 100...
Page 98: ...Your notes ThermSelect 98 100 12 Index...
Page 100: ...Your notes ThermSelect 100 100...