Fig. 30:
Dimensions RSBT 4016, 4025, 4032 EV 11
Number of
flashing
signals
red LED
Status
Action
2
Incorrect phase sequence Physical change
3
Power supply not in accor-
dance with regulations
Auto reset with 5 min.
recovery
4
Frequency not in accor-
dance with regulations
Auto reset with 5 min.
recovery
5
Rotor blocking status
(while ramping)
Auto reset with 5 min.
recovery
6
Startup time > 1 sec.
Auto reset with 5 min.
recovery
7
Excess temperature
Auto reset
8
Excess current
(during bypass)
Auto reset with 5 min.
recovery
9 Supply
voltage
unbalance
Auto reset with 5 min. re-
covery, provided that all
phases (L1, L2, L3) are
connected.