5. Technical Data
ThermSelect®
24/100
5.3 Technical
data
Air+Brine/Water Head Pumps* ThermSelect
®
15 to 41
ThermSelect
®
..
15
19
28
34
41
Output A2/W35* Nominal heating capacity
kW
16,2
20,5 28,8 35,4 43,0
Power consumption condenser*
kW
3,3
4,6 6,1 7,5 9,2
Cooling capacity*
kW
13,0
16,1 23,1 28,2 34,3
Performance number*
COP
4,7
4,4
4,6
4,5
4,5
Output B0/W35* Nominal heating capacity
kW
15,1
19,1 26,9 33,1 40,2
Power consumption condenser**
kW
3,3
4,5 6,0 7,4 9,0
Cooling capacity**
kW
12,0
14,9 21,2 26,0 31,7
Performance number**
COP
4,4
4,1
4,3
4,3
4,3
Refrigerant
R 407 c for hot water temperatures up to 55 °C
Refrigerant dosage for max. 20 m line
length***
kg
10,0
12,0 15,5 20,2 20,7
Refrigerant lines
Liquid
(1)
mm
15 18
22
Suction gas (2)
28
35
42
Thawing (3)
12
15
18
Nominal power consumption
A
7,4
12,6
14,3
16,2
18,6
Operating current, max.
A
11,8
16,0
21,0
25,0
32,0
Starting current with soft-start
A
37,0
49,5 63,5 83,5 99,0
Blocked rotor current
A
74,0
99,0
127,0
167,0
198,0
Power circuit breaker / Automatic circuit breaker,
slow (C characteristic)
A 3x25
3x32 3x40 3x63
Recommended wire gauge
mm²
3x4.0
3x6.0
3x10.0
Electric connection Compressor
control
current
3NPE, 400 V
1NPE, 230 V
Protection class heat pump according to
EN 60529
IP
40
Protection class split evaporator according to
EN 60529
IP
54
Evaporated air flow rate, nominal
m³/h
5220
6670
10820
16010
14800
Sound pressure at 5 m
dB (A)
35
41
43
53
53
Mass flow heating system nominal
kg/h
2630
3340
4700
5780
6900
Pressure loss heating water at nominal flow rate
kPa
5,8
3,2
4,5
4,2
5,2
Heating connection
AG“
1
1½
Outer dimensions W x D x H inner part
mm
690x600x900
1030x730x900
Outer dimensions W x D x H outer part
mm
2155x880x1030
3080x880x1030
Weight of inner part
kg
198
225
238
250
258
Weight of outer part
kg
138
152
202
223
* Heating capacity and COP at A2/W35 as well as source side 3 K and heating side 5K spread
**
Output ratings at B0/W35 as well as source side 3K and heating side 5K spread
***
When changes to refrigerant lines lead to lengths exceeding 20 m, refrigerant dosage will change as follows: Pipe
with max. Ø 22 mm +/- 100 g/m, pipe with max. Ø 28 mm +/- 150 g/m, pipe with max. Ø 35 mm +/- 200 g/m
NOTE!
Refrigerant R407C for heating water temperatures up to H55 °C.
Summary of Contents for ThermSelect
Page 1: ...ThermSelect As of 9 March 2011...
Page 22: ...5 Technical Data ThermSelect 22 100 5 2 Identification plate Fig 4 Sample identification plate...
Page 25: ...ThermSelect 5 Technical Data 25 100...
Page 31: ...ThermSelect 5 Technical Data 31 100...
Page 45: ...ThermSelect 6 Assembly 45 100 Fig 10 Sensor cable heat source inlet 5...
Page 72: ...8 Maintenance ThermSelect 72 100 8 4 Spare part drawing and legend Fig 37...
Page 96: ...Your notes ThermSelect 96 100...
Page 97: ...ThermSelect Your Notes 97 100...
Page 98: ...Your notes ThermSelect 98 100 12 Index...
Page 100: ...Your notes ThermSelect 100 100...