7. Operation Startup
ThermSelect®
64/100
Pump control
-
Circulating pump control
-
Unscrew pump stopper and turn pump shaft as illustrated below.
-
Screw pump stopper back in
-
Caution: Collect drops
Fig. 32:
Loosen pump stopper
Switching on the device
After proper inspection of the installation, the power connection can
be switched on. For this, activate the installed power switch and au-
tomatic circuit breaker.
Refrigerant dosage
The quantity of refrigerant is determined during operation by mea-
suring and comparing the refrigerant condensation temperature and
the heat pump flow temperature. The heat pump / compressor must
be activated for min. of 10 min. and a flow temperature of approx.
50°C must be reached before measurement or the results will not be
reliable and the amount of refrigerant indicated will not be correct.
The difference between both of these temperatures should be be-
tween 0 and 3 K (condensation temperature - flow temperature).
Test for leak-tightness
Once operating, the refrigerant circuit must be rechecked for lea-
kage using a sensitive leak detection device/substance.
Summary of Contents for ThermSelect
Page 1: ...ThermSelect As of 9 March 2011...
Page 22: ...5 Technical Data ThermSelect 22 100 5 2 Identification plate Fig 4 Sample identification plate...
Page 25: ...ThermSelect 5 Technical Data 25 100...
Page 31: ...ThermSelect 5 Technical Data 31 100...
Page 45: ...ThermSelect 6 Assembly 45 100 Fig 10 Sensor cable heat source inlet 5...
Page 72: ...8 Maintenance ThermSelect 72 100 8 4 Spare part drawing and legend Fig 37...
Page 96: ...Your notes ThermSelect 96 100...
Page 97: ...ThermSelect Your Notes 97 100...
Page 98: ...Your notes ThermSelect 98 100 12 Index...
Page 100: ...Your notes ThermSelect 100 100...