ThermSelect®
9. Troubleshooting
75/100
Fault
Cause
Remedy
Fault with con-
denser motor con-
denser overload
(overheating of the
motor winding)
Failure of a phase
Check supply line of 3-phase current
Mechanical failure due to lack of lubrication Request factory service
Winding protection defective
Replace winding protection
Low refrigerant level
Request factory service
Defect in the refrigerant regulation
Request factory service
Operation with incorrect refrigerant
Request factory service
Pressure gas temperature too high
Request factory service
Fault current (FI)
circuit breaker ac-
tivates
Wrong allocation of neutral lead for spe-
cial/normal tariff
Check device wiring
heating pump
locked
Special tariff supply line interrupted (off-time
preset by utility company);
bivalence point undercut
Check blocking times for the special tariff
connection;
check parameters (RVS 61, Line 2910)
Evaporator ices up
quickly
High humidity and temperatures of 3-8°C
lead to quick icing up of the evaporator.
Decrease time until forced thaw (parameter
line 2963)
Summary of Contents for ThermSelect
Page 1: ...ThermSelect As of 9 March 2011...
Page 22: ...5 Technical Data ThermSelect 22 100 5 2 Identification plate Fig 4 Sample identification plate...
Page 25: ...ThermSelect 5 Technical Data 25 100...
Page 31: ...ThermSelect 5 Technical Data 31 100...
Page 45: ...ThermSelect 6 Assembly 45 100 Fig 10 Sensor cable heat source inlet 5...
Page 72: ...8 Maintenance ThermSelect 72 100 8 4 Spare part drawing and legend Fig 37...
Page 96: ...Your notes ThermSelect 96 100...
Page 97: ...ThermSelect Your Notes 97 100...
Page 98: ...Your notes ThermSelect 98 100 12 Index...
Page 100: ...Your notes ThermSelect 100 100...