5. Technical Data
ThermSelect®
34/100
Electrotechnical data controller
Input
(controller)
Rated voltage
AC 230 V (
±
10%)
Rated frequency
50/60 Hz
Max. power consumption
11 VA
Fuse protection of supply lines
max. 10 A slow
Wire gauge
internal resistance
1 wire: 1.0 mm
2
- 1.5 mm
2
> 100 k
Ω
Terminal wir-
ing
(Outputs)
Wire or stranded wire (twisted or with wire end
ferrule):
1 wire: 0.5 mm
2
...2.5 mm
2
2 wires 0.5. mm
2
..1.5 mm
2
Functional -
data
Mode of functioning according to EN 60730
1b (automatic function)
Inputs
Digital inputs H1, 3
Extra-low voltage for potential-free extra-low
voltage capable contacts:
Voltage with opened contact: DC 12 V
Voltage at closed contact: DC 3 mA
Analogue input H1, 3
Extra-low voltage
work area: DC (0...10) V
internal resistance: > 100 k
Ω
Line inputs EX1…EX7, E9-E11
AC 230 V (
±
10 %)
Internal resistance > 100 k
Ω
Sensor input B9
Sensor inputs B1, B3, B4, B21, B41, B71, B81,
B82, B91 and B92
Sensor inputs BX1…BX5
NTC1k (QAC34)
NTC10k (QAZ36, QAD36)
NTC10K (QAZ36, QAD36), PT 1000
Permitted sensor lines (Cu)
At wire gauge:
Max. length:
0.25 0.5 0.75 1.0 1.5
(mm
2
)
20 40 60 80 120
(m)
Outputs
Relay outputs Q2, Q3, Q8, Q9, QX1..QX6, Y1,
Y2
Rated current range
Maximum starting current
Maximum total current (all relays)
Rated
current
range
AC 0.02...2 (2) A
15 A during
≤
1 s
AC 6 A
AC (24...230) V (for potential-free outputs)
Output Q4 Mod rated current range
ON/OFF mode
RPM
controller
Maximum starting current
AC 0.05...2 (2) A
AC 0.05...1.4 (1.4) A
4 A during
≤
1 s
Analogue output UX
Output voltage
Current
load
Ripple
Precision zero point
Error remaining area
Output is short-circuit-proof
Uout = 0 ... 10.0 V
±2 mA RMS; ±2.7 mA peak
≤
50 mVpp
< ± 80 mV
≤
130 mV
Summary of Contents for ThermSelect
Page 1: ...ThermSelect As of 9 March 2011...
Page 22: ...5 Technical Data ThermSelect 22 100 5 2 Identification plate Fig 4 Sample identification plate...
Page 25: ...ThermSelect 5 Technical Data 25 100...
Page 31: ...ThermSelect 5 Technical Data 31 100...
Page 45: ...ThermSelect 6 Assembly 45 100 Fig 10 Sensor cable heat source inlet 5...
Page 72: ...8 Maintenance ThermSelect 72 100 8 4 Spare part drawing and legend Fig 37...
Page 96: ...Your notes ThermSelect 96 100...
Page 97: ...ThermSelect Your Notes 97 100...
Page 98: ...Your notes ThermSelect 98 100 12 Index...
Page 100: ...Your notes ThermSelect 100 100...