6. Assembly
ThermSelect®
54/100
Highly reliable spring clips are used as connection terminals. The
clips are opened with the appropriate, included tool (small screw
driver) which is inserted in the respective square opening and is
then moved in the direction away from the lead intake opening.
Electrical connection for compres-
sor
The connection for the supply lines from the special tariff (3c400 V,
N, PE) occur directly on the motor protection switch (L1, L2, L£) and
for N and PE on the relevant terminal connectors on the top-hat rail.
Fig. 19:
Special tariff connection
Electrical connections for RVS con-
troller
Component
Connection to
Line on site
Sensor outside
RVS controller,
slot k,
terminal B9, M
Cable interchangea-
ble
Sensor source inlet
49.0
RVS controller,
slot r,
terminal B91, M
Cable interchangea-
ble
Sensor evaporator
48.1
RVS controller,
slot s,
terminal B84, M
Cable interchangea-
ble
Control signal 0-10 V
RVS controller,
slot z,
terminal UX, M
Terminal connectors
ventilator
terminal 0-10
V/PWM, GND
Comply with polarity
Summary of Contents for ThermSelect
Page 1: ...ThermSelect As of 9 March 2011...
Page 22: ...5 Technical Data ThermSelect 22 100 5 2 Identification plate Fig 4 Sample identification plate...
Page 25: ...ThermSelect 5 Technical Data 25 100...
Page 31: ...ThermSelect 5 Technical Data 31 100...
Page 45: ...ThermSelect 6 Assembly 45 100 Fig 10 Sensor cable heat source inlet 5...
Page 72: ...8 Maintenance ThermSelect 72 100 8 4 Spare part drawing and legend Fig 37...
Page 96: ...Your notes ThermSelect 96 100...
Page 97: ...ThermSelect Your Notes 97 100...
Page 98: ...Your notes ThermSelect 98 100 12 Index...
Page 100: ...Your notes ThermSelect 100 100...