3. Inputs and Outputs: technical specifications
TABLE 1 : CONNECTOR CN1
1
Exc-
Excitation
Continuous Rating: 4Adc
Transitory Rating:12Adc at peak
2
Aux/Exc+
3
Aux/Exc+
Power
40÷270 Vac, Frequency: 12÷72Hz
(2)
(1)
4
UFG
Sensing
Range 2
Range 2: 150÷300 Vac
Burden: <1VA
U channel
5
UFG
6
UHG
Sensing
Range 1
Range 1: 75÷150 Vac
Burden: <1VA
7
UHG
8
UHB
Jumper
Range1
Short for sensing
75÷150 Vac
9
UFB
10
UFB
Board reference
11
UFB
12
UFB
13
-
Not present
14
VFG
Sensing
Range 1: 75÷150 Vac
Burden: <1VA
V channel, to be
connected in parallel to
U channel in case of
single phase sensing
15
VHG
Sensing
Range 1
16
VHB
Scala 2: 150÷300 Vac
Burden: <1VA
17
VFB
Range 2
18
-
Not present
19
WFG
Sensing
Range 1: 75÷150 Vac
Burden: <1VA
W channel, unused
(with shorted inputs)
in case of single phase
sensing
20
WHG
Sensing
Range 1
21
WHB
Range 2: 150÷300 Vac
Burden: <1VA
22
WFB
Range 2
!"#
TABLE 2 : CONNECTOR CN3
23
Common
Active
protections output
$#%&'
Current: 100mA
Voltage: 30V
Max length: 30m
(3)
Both activating alarm
and delay time are
programmable
24
A.P.O.
25
Common
Jumper 50/60Hz
Type: Not insulated
Max length: 3m
Selection of underspeed
protection threshold
(4)
26
50/60Hz
27
0EXT
Jumper for remote voltage
control 0÷2,5Vdc
Type: Not insulated
Max length: 3m
Short for 0÷2,5Vdc input
or potentiometer
28
JP1
29
Input for remote voltage
Type: Not insulated
Max length: 30m
(3)
Regulation: ±10 %
(5)
(
)*+!,-
30
PEXT
( %)*+!, )).
/%)*0
31
JP2
Pext Jumper
Type: Not insulated
Max length: 3m
Short for 0÷2,5Vdc input
or potentiometer
32
±10V
control ±10 Vdc
Input: ±10Vdc
/%120
0EXT
Note 1) The terminals are connected to each other on the board: 2 with 3, 4 with 5, 6 with 7, 9 with 10, 11 and 12.
Note 2) Minimum power voltage 40 Vac at 15 Hz, 100 V at 50 Hz, 115 V at 60 Hz
Note 3) With external EMI filter (3m without EMI filter)
Note 4) 50·(100%-
Hz%) or 60·(100%-
Hz%) where
Hz% is the position relative to the Hz trimmer or the percen
tage value of parameter P[21]
Note 5) Value not to be exceeded. The effective range depends on parameter P[16]
Summary of Contents for DER1
Page 10: ...DER1 digital regulator instruction manual rev 03 pag 10 SCC0158 Three phase sensing 75V 150V...
Page 11: ...DER1 digital regulator instruction manual rev 03 pag 11 SCC0159 Three phase sensing 150V 300V...
Page 12: ...DER1 digital regulator instruction manual rev 03 pag 12 SCC0160 Single phase sensing 75V 150V...
Page 13: ...DER1 digital regulator instruction manual rev 03 pag 13 SCC0161 Single phase sensing 150V 300V...
Page 14: ...DER1 digital regulator instruction manual rev 03 pag 14 SCC0202 Single phase sensing 300V 600V...