background image

DER1 digital regulator instruction manual - rev. 03 - pag. 19 

Bit 

Value 

Function 

/

B0 

1  Not used

 

B1 

2  Periodical reference variation

 

B2 

4  Automatic voltage offset compensation

(1)

 

B3 

8  Not used

 

B4 

16  Enable hardware jumper 50/60Hz

 

B5 

32  Free for future use

 

B6 

64  Force three-phase sensing

 

B7 

128  External location reference L[49] 

(2) 

and activation of saturation in the event of overflow

 

B8 

256  Enable VOLT TRIMMER

 

B9 

512  Enable STAB TRIMMER

 

B10 

1024  Enable Hz TRIMMER

 

B11 

2048  Enable AMP TRIMMER

 

B12 

4096  Enable external analogical input

 

B13 

8192  Enable external DAC

 

B14  16384  60 Hz setting in the event of disabling of the 50/50 Hz hardware jumper

 

B15  32768  Reserved

 

TABLE 7 : BIT FUNCTION OF THE CONFIGURATION WORD (PARAMETER P[10] ) 

NOTE 1: only with single phase reference

 

NOTE 2: if analogical input is disabled

 

NOTE 3: for analogical input

 

3. RAM location reference, activation of saturation in analogical remote control 

 

The 

RAM  Voltage  CTRL 

Flag  (corresponding  to  bit  7  of  the  P[10]  configuration  word)  performs  two 

functions:  
1.  If the Pext hardware input is enabled (Flat Ext. Input corresponding to bit 12 of the P[10] configuration 

word), as previously  described,  the 

RAM  Voltage  CTRL  Flag 

activates saturation  of output  voltage 

when  the  analogical  control  voltage  reaches  the  limit  foreseen  for  input,  to  which  it  is  applied  (see 
Para. 8 Remote control of voltage).  

 

If saturation is enabled, in the event of removal of the Vext/Pext connection (due to accidental 
opening, for example) the voltage goes to the maximum value set in parameter P[16] (+14% by 
default).

 

2.  When Pext  is  disabled  by  hardware,  the  indicated flag  defines  the  value  to  be  used by  the  software 

control of the output voltage. If RAM Voltage CTRL is deactivated (B7=0), the non volatile parameter P
[15]  is  used  (therefore  following  shut  down  and  restart  of  the  regulator,  the  last  value  memorised 
remains  set):  on  the  start  up  the  location L[49]  is  initialised  with  the  value of parameter  P[15] and  is 
kept  aligned  to  that  value.  Editing  of  location  L[49]  has  no  effect  in  this  working  condition.  If  RAM 
Voltage  CTRL  is  active  (B7=1)  the  volatile  location  L[49]  is  used  for  software  remote  control  of  the 
output voltage (when the regulator is energized, the value is stored. If the regulator is shut down,  the 
value is lost). This function is particularly useful for the applications of alternators in parallel with grid, 
when the regulation of the reactive power exchanged is controlled by means of a third party supplied 
digital supervisor. 

FLAG 

RAM  

Voltage CTRL

 

P[10] Bit B7 

FLAG 

Ext. Input

 

P[10] Bit B12 

Output voltage control type 

 

 

Analogical without saturation 

 

 

Analogical with saturation 

 

 

Digital - Parameter P[15] 

 

 

Digital - Location L[49] 

TABLE 8 :  REMOTE VOLTAGE CONTROL FLAGS FUNCTION 

 

Summary of Contents for DER1

Page 1: ...64 93 8552 20 53 41 831 429 08 12 3843 20 46 81 383 227 86 73 3812 21 46 40 4862 44 53 42 3532 37 68 04 8412 22 31 16 342 205 81 47 863 308 18 15 4912 46 61 64 846 206 03 16 812 309 46 40 845 249 38 7...

Page 2: ...Status Word Location L 39 pag 18 SETTING OF VOLT STAB AMP and Hz PARAMETERS pag 19 1 Voltage pag 19 1 1 Setting voltage pag 19 1 2 Soft Start pag 19 1 3 Slow voltage variations pag 20 2 Stability pag...

Page 3: ...gured to obtain the best performance most of the settings are stored in a non volatile integrated memory EEPROM The first time the regulator is turned on a default configuration will be present which...

Page 4: ...ized conditions load temperature Transient voltage drop and overvoltage within 15 Voltage recovery time within 3 of the value set in less than 300 msec Programmable Soft start Parameters VOLT STAB AMP...

Page 5: ...Range 2 TABLE 2 CONNECTOR CN3 23 Common Active protections output Current 100mA Voltage 30V Max length 30m 3 Both activating alarm and delay time are programmable 24 A P O 25 Common Jumper 50 60Hz Typ...

Page 6: ...ation overcurrent protection TABELLA 3 TRIMMERS Fig 1 INSTALLATION Upon receipt of the digital regulator perform a visual inspection to ensure that no damage has been sustained during transportation a...

Page 7: ...or connections depend on the application and excitation system Figure 1 shows the functional aspect of the connection points to the regulator An error in connection may have deadly consequences for th...

Page 8: ...tes Series star H SCC0160 H SCC0158 F N A F N A 530 550 575 600 690 760 800 920 960 from 520 to 1000 F SCC0161 F SCC0159 1200 from 1100 to 2000 F SCC0202 2 channels in series Parallel star 190 200 208...

Page 9: ...rom the Configuration Menu 4 The parameter present in parameter P 5 if three phase sensing or p 6 if single phase sensing has to be calibrated Calibration should be adjust in order to obtain 225V from...

Page 10: ...DER1 digital regulator instruction manual rev 03 pag 10 SCC0158 Three phase sensing 75V 150V...

Page 11: ...DER1 digital regulator instruction manual rev 03 pag 11 SCC0159 Three phase sensing 150V 300V...

Page 12: ...DER1 digital regulator instruction manual rev 03 pag 12 SCC0160 Single phase sensing 75V 150V...

Page 13: ...DER1 digital regulator instruction manual rev 03 pag 13 SCC0161 Single phase sensing 150V 300V...

Page 14: ...DER1 digital regulator instruction manual rev 03 pag 14 SCC0202 Single phase sensing 300V 600V...

Page 15: ...DER1 digital regulator instruction manual rev 03 pag 15 SCC0203 Single phase sensing 300V 600V generator in threephase ZIG ZAG connection...

Page 16: ...voltage can be controlled by software as well with the P 19 The excursion range and gain of the remote control can be set independently by software despite the output voltage control device system us...

Page 17: ...protection of up to 20 with respect to the nominal speed value set by the 50 60 jumper if activated or by the 50 50 box in the Configuration menu at 50 Hz the threshold can be calibrated from 40 Hz to...

Page 18: ...6 126 126 18 Step limitation reference 20 20 0 8 19 Vout Reference 6 9 9 0 0 8 20 Stability 6 9 9 16384 16384 8 21 A D A 6 9 9 16384 16384 FG 8 22 4 6 9 9 16384 16384 8 23 2 6 9 9 9000 9000 2 24 2 6...

Page 19: ...ltage reaches the limit foreseen for input to which it is applied see Para 8 Remote control of voltage If saturation is enabled in the event of removal of the Vext Pext connection due to accidental op...

Page 20: ...ated voltage tenths of volts 37 Second status word 0 900 Read only Frequency tenths of Hz 38 Third status word 16bit Read only Active alarms 39 Fourth status word 16bit Read only Active configuration...

Page 21: ...cale H on sensing inputs 4 5 9 10 11 12 14 17 and 19 22 between 150 300 Vac scale F There are two ways to set from minimum to maximum value 1 With the VOLT trimmer which must be enabled by the Configu...

Page 22: ...to obtain the desired gain i e parameter P 11 4 coefficient 24 16 The regulator diagram is shown in figure 6 KP KI s Ref Feedback Error PIout figure 6 Regulator Diagram 3 EXCITATION OVERCURRENT 3 1 D...

Page 23: ...nderspeed protection threshold rotating the Hz trimmer counter clockwise if it has been enabled from the Configuration Menu or by entering 0 at parameter P 21 2 Rotate the AMP trimmer completely in th...

Page 24: ...proportionately reduced as indicated in figure 8 Parameter P 23 sets the slope of the voltage frequency curve the default value is 9000 An increase in the value of P 23 involves a greater reduction of...

Page 25: ...ues between 65535 1 and 32768 32767 lower the threshold proportionately to 50 Hz and 60 Hz respectively values between 0 and 32767 raise the threshold proportionately respectively to 60 Hz and 72 Hz r...

Page 26: ...ge a decrease in the value of P 24 will cause a lower reduction in voltage up to the limit of P 24 0 which means that no reduction in voltage will take place WARNING If the voltage is not lowered enou...

Page 27: ...age 5 Excitation Overcurrent APO Reduction of excitation current 6 Underspeed APO V F Ramp 7 Overspeed APO TABLE 12 ALARMS LIST TABLE 13 ALARM FLAGS AT LOCATION L 38 6 5 J 9 6 6 9 J 6J J 5 5 J J 12 1...

Page 28: ...ted short circuit time goes from 0 1 to 25 5 seconds programmable in 100 ms steps then the regulator is blocked after saving DD and TT and signals the STOP status With the time in short circuit set on...

Page 29: ...for which the APO must be activated obtaining a number B Example since it is desired to activate the APO in the case of over voltage and overspeed the formula is B 2 64 66 b Multiply the delay it is...

Page 30: ...serial interfaces available on the DI1 communications unit are RS232 without handshake 3 wires on CN3 connector _____ RS485 two wires half duplex on CN4 connector DTE 1 Tx RTSRx RTS The connection be...

Page 31: ...ector CN1 terminals 1 and 4 1 through a dedicated source AC 40V 15Hz 270V 72Hz or DC 40V 380V 3 Alternatively on connector CN5 terminals 1 and 2 through a completely isolated source in DC 9 14V WARNIN...

Page 32: ...ational parameters reading of stored alarms A standard serial cable may be used with 9 pins SUB D connectors TABLE 18 CONNECTOR CN4 Pin N Description Notes 1 485 A RS485 channel A Insulated 2 485 B RS...

Page 33: ...regulator instruction manual rev 03 pag 33 Fig 12 RS232 connection between one DSR regulator and PC through DI1 digital interface Fig 13 R485 connection between DSR regulators and PC through DI1 digit...

Page 34: ...tor 15 goes from red to green IMPORTANT The communication may take place only if all three of the indicators Connected 16 Com STAT 15 and Com ERROR 14 are green The ADDRESS window indicates the slave...

Page 35: ...tings files to and from the regulator which have the extension dat The list of parameters is shown in table 6 There are three possible options 1 Upload Data The Upload window opens The key Open allows...

Page 36: ...equency protection threshold equivalent to Hz 22 16384 Excitation overcurrent threshold equivalent to AMP 23 9000 V F slope 24 6000 V F slope at start up 25 20 Short circuit time in tenths of a second...

Page 37: ...1 digital regulator instruction manual rev 03 pag 37 Fig 15 DSR Terminal User Interface Fig 16 Configuration Menu 1 3 2 4 6 5 9 8 7 12 14 16 17 15 11 10 13 31 18 19 20 21 22 23 32 33 24 25 26 27 28 29...

Page 38: ...parameters requested from the regulator 9 Activation of updating almost in real time 10 Visualisation of the regulator status voltage frequency active alarms configuration 11 50 60Hz Jumper inserted...

Reviews: