DER1 digital regulator instruction manual - rev. 03 - pag. 6
4. Block diagram
Name
Function
Notes
VOLT
Voltage Calibration
From 75Vac to 150Vac or from 150Vac to
300Vac, see paragraph “Setting the voltage”
STAB
Calibration of dynamic response
Adjustment of proportional gain, see paragraph
on “Stability”.
Hz
Calibration of underspeed protection
intervention threshold
Variation up to -20% with respect to the nominal
speed value set in parameter 50/60.
AMP
Calibration of excitation overcurrent
protection
See paragraph “Calibration of excitation
overcurrent protection”
TABELLA 3: TRIMMERS
Fig 1
INSTALLATION
Upon receipt of the digital regulator, perform a visual inspection to ensure that no damage has been
sustained during transportation and movement of the equipment. In the event of damage, advise the
shipper, the insurance company, the seller or Mecc Alte immediately. If the regulator is not installed
immediately, store it in its original packaging in a dust and humidity-free environment.
The regulator is normally installed in the generator terminal box. It is fixed with two M4x25 screws and
must be installed in a location where the temperature does not exceed the environmental conditions
foreseen. Refer to the attached drawings for dimensions and displacement.
Summary of Contents for DER1
Page 10: ...DER1 digital regulator instruction manual rev 03 pag 10 SCC0158 Three phase sensing 75V 150V...
Page 11: ...DER1 digital regulator instruction manual rev 03 pag 11 SCC0159 Three phase sensing 150V 300V...
Page 12: ...DER1 digital regulator instruction manual rev 03 pag 12 SCC0160 Single phase sensing 75V 150V...
Page 13: ...DER1 digital regulator instruction manual rev 03 pag 13 SCC0161 Single phase sensing 150V 300V...
Page 14: ...DER1 digital regulator instruction manual rev 03 pag 14 SCC0202 Single phase sensing 300V 600V...