Technical Manual Glass Room Temp. Contr. SCN-RT1Gx.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
70
7.1.2 Type of thresholds: Control value & Delta T
The following settings are available:
ETS-text
Dynamic range
[default value]
comment
Type of thresholds: Control value
Threshold level 1
0%
–
100%
[10%]
Below this threshold all levels are
switched off, above this threshold level
1 is switched on
Threshold level 2
0%
–
100%
[30%]
Below this threshold level 1 is switched
on, above this threshold level 2 is
switched on
Threshold level 3
0%
–
100%
[50%]
Below this threshold level 2 is switched
on, above this threshold level 3 is
switched on
Threshold level 4
0%
–
100%
[70%]
Below this threshold level 3 is switched
on, above this threshold level 4 is
switched on
Hysteresis
0%-20%
[5%]
Hysteresis for the switchover of the
output stage
Type of thresholds: Delta T
Threshold level 1
1,0K
–
10,0K
[2,0K]
Below this threshold all levels are
switched off, above this threshold level
1 is switched on
Threshold level 2
1,0K
–
10,0K
[4,0K]
Below this threshold level 1 is switched
on, above this threshold level 2 is
switched on
Threshold level 3
1,0K
–
10,0K
[6,0K]
Below this threshold level 2 is switched
on, above this threshold level 3 is
switched on
Threshold level 4
1,0K
–
10,0K
[8,0K]
Below this threshold level 3 is switched
on, above this threshold level 4 is
switched on
Hysteresis
0,1K-2,0K
[0,5K]
Hysteresis for the switchover of the
output stage
Type of thresholds: Control value & Delta T
Total number of steps
2-4
[4]
defines the number of steps for the
Ventilation control
Send output cyclic
Disable
1 min
–
60 min
Parameter activates the cyclic sending
of all output objects
Table 54: Parameter output step-switch