![MDT SCN-RT1GS.01 Technical Manual Download Page 13](http://html1.mh-extra.com/html/mdt/scn-rt1gs-01/scn-rt1gs-01_technical-manual_1757458013.webp)
Technical Manual Glass Room Temp. Contr. SCN-RT1Gx.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1 •
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
13
14
Heating disable object
Disable heating
DPT 1.003
recieve
Controller
diasables heating
Visu, Opereating
keys, Control unit
Can be activated in the settings
when the controller is set to
heating.
15
Cooling disable object
Disable cooling
DPT 1.003
recieve
Controller
diasables cooling
Visu, Opereating
keys, Control unit
Can be activated in the settings
when the controller is set to
cooling.
17
Heating request
Send request
DPT 1.001
send
Controller sends
heating request
Actuator for
switching the
heati g pu p…
Can be activated in the settings
when the controller is set to
heating.
18
Cooling request
Send request
DPT 1.001
send
Controller sends
cooling request
Actuator for
switching the
ooli g pu p…
Can be activated in the settings
when the controller is set to
cooling.
19
Heating/Cooling
switchover
0 = heating, 1 = cooling
DPT 1.001
receive
Controller
switches between
heating and
cooling
Visu, Opereating
keys, Control unit
Can be activated in the
parameter when the controller
is set to heating and cooling.
20
Outside temperature
Read external sensor
DPT 9.001
receive
Controller receives
temperature from
outside sensor
Outdoor
temperature
sensor
Object is shown when the
guiding is activated in the
parameter
21
Max memory value
Read memory
DPT 9.001
send
Controller sends
max. temperature
Visu, Display,
Diagnostic
…
Object is shown when the
min/max values are activated
22
Min memory value
Read memory
DPT 9.001
send
Controller sends
min. temperature
Visu, Display,
Diag osti …
Object is shown when the
min/max values are activated
23
Min/Max Memory Reset
Reset memory
DPT 1.001
receive
Controller resets
min/max values
Visu, Opereating
keys, Control unit
Object is shown when the
min/max values are activated