7.3 Step switch simply
The step switch simply has the same functionality as the normal step switch, described in 7.1 Step
switch bit coded. Only the output stage is different. At each increase of a stage, the previous level
and the new level is turned on. This behavior becomes also clear from the communication objects:
Number
Name
Length
Usage
39
Level 1
1 Bit
Switching level 1
40
Level 1+2
1 Bit
Switching level 1+2
41
Level 1+2+3
1 Bit
Switching level 1+2+3
42
Level 1+2+3+4
1 Bit
Switching level 1+2+3+4
Table 60: Communication objects - step switch simply
7.4 Step switch as Byte
The “tep s it h as B te o tai s of a stead output alue. Up to le els a e defi ed ith a
absolute value (0-100%). The fifth level is the off-state, which sends the value 0%.
The following figure shows an example for the output of the step switch as Byte:
Figure 38: Example output - Step switch as Byte