Manual setpoint value
offset
Increase/Reduction
(1 = + adjusted step,
0 = - adjusted step)
DPT 1.001
receive
Controller receives
setpoint value
offset via a 1 Bit
object
Visu, Operating
keys, Control unit,
Display,
Diag osti , …
Object is shown when
pa a ete “etpoi t alue
offset ia is set to Bit o je t
and shifts the set value
depending on the current
setpoint. The amount of
displacement can be set in the
parameters.
Table 2: Overview communication objects - Room Temperature Controller
3.1.3 Ventilation Control
Objects for Ventilation Control:
38
Ventilation Control
Block
DPT 1.003
receive
Controller locks
ventilation control
Visu, Operating
keys, Control unit,
Displa , …
Object is only shown when the
locking function was activated
in the settings
39
Ventilation Control
Level 1
DPT 1.001
send
Controller
switches level 1
Actuator for
controlling a
ventilation
system, Fan-Coil
actuator
Object is shown at the setting
step switch bit coded
39
Ventilation Control
Bit 0
DPT 1.002
send
Controller
switches Bit 0
Actuator for
controlling a
ventilation
system, Fan-Coil
actuator
Object is shown at the setting
step switch binary coded