The PI control continuous is a continuous controlling with proportional amount, the Proportional
range, and an integral amount, the reset time. The size of the proportional range is indicated in K,
whereas the I-amount is indicated in minutes.
The control value is controlled in steps from 0% to the adjusted maximum (have a look at 4.5.2.1 Max
value of control value) for the PI-control. A big deviation causes at normal direction, a big control
value to eliminate the deviation as fast as possible.
6.4.2.1 Max value of control value
B the setti g Ma alue of o t ol alue a e adjusted hi h a i u alue the o t ol alue
can assume. To prevent switching processes at large control values, a maximum can be defined by
the setti g Ma alue of o t ol alue . “o the o t ol alue a ot e eed this alue.
6.4.2.2 Heating/ cooling system
The control parameter (P-amount and I-amount) are adjusted by the setting for the used heating/
cooling system. You can use preset values, which fit to determined heating or cooling systems, or
parameterize the proportional range and the reset time freely. The preset values for the
corresponding heating or cooling system are based on empirical values and lead often to good
controlling results.
By choo
si g Adjust e t ia o t ol pa a ete , the p opo tio al a ge a d the eset ti e a e
parameterized freely. This setting requires a good knowledge in the field of control technology.
6.4.2.3 Proportional range
The proportional range represents the P-component of a controller. The P-component of a controller
results in a proportional increase of the control value in accordance to the control difference.
A small proportional band leads to a rapid settling of the error signal. The controller reacts almost
abruptly at a small proportional range and set the control variable even for small control differences
almost to the max. Value (100%). If the proportional range is too small, the risk of overshooting is
very large.
A proportional range of 4K sets the control value to 100% when the error (difference between the
setpoint and the current temperature) at 4 ° C. Thus, in this setting would be a deviation of 1 ° C lead
to a control value of 25%.