4
Heat alarm
Send alarm
DPT 1.001
send
Controller sends
state
Visu, Display,
Diagnostic,
Additio al stage,…
Communication object is
shown when alarms are active
5
External sensor
Read external sensor
DPT 9.001
receive
Controller receives
external
temperature
Input for external
temperature
Communication object is
shown when sensor is set to at
least 10% external sensor
6
Setpoint comfort
Set setpoint
DPT 9.001
receive
Controller receives
new absolute
setpoint
Visu, Opereating
keys, Control unit
Object is permanent shown
when the controller is active. A
new setpoint can be set via this
object.
7
Manual setpoint value
offset
Reduction/Increase
DPT 9.002
receive
Controller receives
new setpoint
offset
Visu, Display,
Operating keys,
Control unit
Object is shown when the
setpoint offset via 2 Byte
object is active. The setpoint is
shifted according to the
current setpoint.
8
Control value heating
Send control value
DPT 1.001/
DPT 5.001
send
Controller sends
manipulated value
Heating actuator,
actuators
Object is shown when the
controller is set to heating. The
DPT depends to the controller
type (two-level & PWM
–
DPT1.001, PI-DPT5.001).