6.3.4 Disable objects
The following figure shows the available settings for the disable objects:
Figure 13: Blocking objects
The following chart shows the dynamic range for this parameter:
ETS-text
Dynamic range
[default value]
comment
Heating disable object
Inactive
Active
activates the blocking object for the
heating process
Cooling disable object
Inactive
Active
activates the blocking object for the
cooling process
Table 36: Blocking objects
Depending to the adjusted controller type, one or two blocking objects are available. The blocking
objects disable the control value. The blocking objects can be used when the heating or cooling
system shall be prevented of an unwanted start.
If the heating must not start at special situations, for example when a window is opened, the
blocking object can be used. Another usage of this function is for example the manual blocking, for
example by a push button, in case of a cleaning process.
The blocking objects have the size of 1 Bit and blocks by sending a logical 1 at the depending
communication object.
The chart shows the relevant communication objects:
Number
Name
Length
Usage
14
Heating disable object
1 Bit
blocks the control value heating
15
Cooling disable object
1 Bit
blocks the control value cooling
Table 37: Communication objects blocking objects