6 Room Temperature Controller
6.1 Temperature Measurement
The following figure shows the menu
T
emperature Measurement :
Figure 6: Temperature Measurement
The table shows the available settings for this menu:
ETS-text
Dynamic range
[default value]
comment
Send actual value after change
of
disable
0,1K - 2,0K
Sending condition for the actual
temperature value
Send actual temperature
cyclically
disable
1 min
–
60 min
Activation of the cyclically sending of
the temperature value
Send min/max value
disable
Send enable
Activation of the sending of min/max
values
Internal sensor correction value
(value*0,1K)
-50
–
50
[0]
Correction of the internal sensor
Internal/external sensor
100% intern
90% intern/ 10% extern
80 % intern/ 20% extern
…
100% extern
Adjustment of the balance between
internal and external sensor
Query the outside temperature
after reset
No
Yes
determines whether the temperature is
to be queried after a reset
Table 14: Paramter temperature measurement