The second opportunity of the manual setpoint offset is the movement of the setpoint depending to
the current a
djusted setpoi t. Fo this a ia t of setpoi t offset, the o je t a ual setpoi t alue
offset is used. “e di g a positi e Kel i alue at this o je t auses a i
e e t of the u e t
setpoint. Sending a negative Kelvin value at this object causes a decrement of the current setpoint.
The setti g a setpoi t offset i di ates the a i al possi le setpoi t o e e t. If the o t olle
is for example set to a basic comfort setpoint of 3K, the setpoint can only be moved manual in the
limits of 18°C and 24°C.
The setti g a setpoi t offset alid fo defi es the s ope of the setpoi t offset. You a hoose
whether the setpoint offset is only valid for the comfort mode or also for the night and standby
mode. The operating mode frost/ heat protection is always independent of the setpoint offset.
The setti g „Reset setpoi t afte ha ge of ode i di ates hethe a setpoi t offset shall e
maintained after a change of mode or not. If this parameter is deactivated, the device will switch to
the adjusted setpoint for the chosen operating mode after every change of mode.
The o
u i atio o je t A tual setpoi t is fo the ue of the u e t setpoi t at the a tual
adjusted operating mode.
The following chart shows the relevant communication objects:
Number
Name
Length
Usage
6
Setpoint comfort
2 Byte
Parameterization of a new absolute comfort
setpoint
7
Manual setpoint value offset
2 Byte
Movement of the setpoint depending to the
current adjusted basic comfort setpoint
29
Actual setpoint
2 Byte
Readout of the actual adjusted setpoint
Table 35: Communication objects setpoint offset