AGZ 026B through 130B
IOMM AGZ-5
Table 22, AGZ 075BM/BS – 130BM/BS, Electrical Wiring, Single Point
(Up to 105°F)
Power Supply
Max. Fuse
Field Wire
AGZ Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Quantity
Wire
Gauge
75C
Recomm’d.
Fuse
Or HACR
Breaker
Size
Or HACR
Breaker
Size
208
358
6
4/0
400
400
230
358
6
4/0
400
400
380
187
3
3/0
225
225
460
150
3
1/0
175
175
075B
575
125
3
#1
150
150
208
380
6
250
450
450
230
380
6
250
450
450
380
219
3
250
250
250
460
171
3
2/0
200
200
085B
575
136
3
1/0
150
150
208
414
6
300
500
500
230
414
6
300
500
500
380
248
3
250
300
300
460
188
3
3/0
225
225
090B
575
146
3
1/0
175
175
208
463
6
350
500
500
230
463
6
300
500
500
380
260
3
300
300
300
460
199
3
3/0
225
225
100B
575
171
3
2/0
175
175
208
528
6 - (2)
300
600
600
230
528
6 - (2)
300
600
600
380
282
3
300
300
300
460
220
3
4/0
250
250
110B
575
182
3
3/0
200
200
208
613
6 - (2)
350
700
700
230
613
6 - (2)
350
700
700
380
323
3
400
350
350
460
248
3
250
250
250
120B
575
198
3
3/0
225
225
208
613
6 - (2)
350
700
700
230
613
6 - (2)
350
700
700
380
361
6
4/0
400
400
460
273
3
300
300
300
130B
575
212
3
4/0
225
225
NOTES:
1.
Units operating in ambient temperatures of 95
°
F (35
°
C) and above must use the Maximum
Fuse or HACR Breaker size.
2.
All Electrical Data notes are on page 49.
3.
(2) indicates that two conduits are required.
4.
Conduit hubs are not supplied.