22
AGZ 026B through 130B
IOMM AGZ-5
Figure 19, AGZ 026B – 130B, Evaporator Pressure Drop
026-030
075-085-090
100-110
120-130
035
040
045
050
055
065-070
060
Minimum Nominal Maximum
Inch-Pound S.I. Inch-Pound S.I. Inch-Pound S.I.
AGZ Unit
Model
gpm
DP ft.
lps
DP kpa
gpm
DP ft.
lps
DP kpa
gpm
DP ft.
lps
DP kpa
026B 41 1.6 2.6 4.7 65 3.9
4.1 11.6 109
10.4
6.9
30.9
030B 45 1.9 2.9 5.7 72 4.7
4.6 14.1 121
12.7
7.6
37.8
035B 50 1.9 3.1 5.6 80 4.6
5.0 13.8 133
12.4
8.4
36.9
040B 58 1.9 3.6 5.7 92 4.7
5.8 14.0 154
12.6
9.7
37.5
045B
64
1.8 4.0 5.4 102 4.5 6.4 13.4 170 12.1 10.7 35.9
050B
71
1.8 4.4 5.4 113 4.5 7.1 13.3 188 12.0 11.9 35.7
055B
78
1.8 4.9 5.3 125 4.4 7.9 13.0 209 11.7 13.2 34.8
060B
86
1.7 5.4 5.2 137 4.3 8.6 12.8 228 11.5 14.4 34.2
065B
92
1.6 5.8 4.9 147 4.1 9.3 12.1 246 10.9 15.5 32.5
070B
98
1.9 6.2 5.6 157 4.6 9.9 13.7 262 12.3 16.5 36.8
075B 111 5.6 7.0 16.5 177 12.5 11.2 37.4 295 30.4 18.6 90.7
085B 119 6.3 7.5 18.9 191 14.3 12.1 42.7 318 34.8 20.1
103.6
090B 128 7.2 8.1 21.4 205 16.2 12.9 48.4 342 39.4 21.6
117.3
100B 146 2.6 9.2 7.7 234 6.1
14.8 18.2 390 15.5
24.6
46.2
110B 161 3.1 10.2 9.2 258 7.3
16.3 21.7 430 18.5
27.1
55.1
120B 180 3.5 11.3 10.4 288 8.9 18.1 26.5 479 24.6 30.2 73.4
130B 194 4.1 12.2 12.1 311 10.4 19.6 30.9 518 28.7 32.7 85.6
NOTE: Minimum and maximum flows are established to ensure the Delta-T for each unit size falls within the 6 - 16°F range for
proper unit control.