58
AGZ 026B through 130B
IOMM AGZ-5
Automatic Adjusted Ranges
The following are setpoints that will be limited based on the option selected.
Evaporator Leaving Water Temperature
Mode Range
Unit Mode = Cool
40 to 60
°
F
Unit Mode = Cool w/Glycol
20 to 60
°
F
Evaporator
Freeze
Temperature
Mode Range
Unit Mode = Cool
37 to 42
°
F
Unit Mode = Cool w/Glycol,
Ice w/Glycol
18 to 42
°
F
Low Evaporator Pressure Hold and Unload
Mode Range
Unit Mode = Cool
55 to 65 Psig
Unit Mode = Cool w/Glycol,
Ice w/Glycol
31 to 65 Psig
Low
Ambient
Lockout
Temperature
VFD Range
VFD = N
35 – 60
°
F
VFD = Y
-2 – 60
°
F
Forced Fan 1,2,3
Number of Fans
Range
4
1 – 2 fans
6
1 – 3 fans
8
1 – 4 fans
Shutdown Alarms
Shutdown alarms (also know as “Stop Alarms” or “Safeties”) execute rapid compressor
shutdown and require manual reset. They are also logged in the Alarm Log.
The following table identifies each equipment protection alarm, gives the condition
that causes the alarm to occur, and states the action taken because of the alarm. If the
alarm is auto-clearing, the reset condition is also shown. Otherwise, the alarm is
manually reset, requiring the operator to clear the alarm.