56
AGZ 026B through 130B
IOMM AGZ-5
Table 37, Digital Inputs
# Description Type
Signal
Signal
1
Unit OFF Switch
UT
0 VAC (Disable)
24 VAC (Enable)
2
Pump Down Switch #1
C1
0 VAC (Disable)
24 VAC (Enable)
3
Evaporator Water Flow Switch
UT
0 VAC (No Flow)
24 VAC (Flow)
4 Open
5 Open
6
Pump Down Switch #2
C2
0 VAC (Disable)
24 VAC (Enable)
7 Open
8 Open
9
Phase Voltage Fault #1 (
See Note 1
)
C1
0 VAC (Fault)
24 VAC (No Fault)
10
Phase Voltage Fault #2 (
See Note 1
)
C2
0 VAC (Fault)
24 VAC (No Fault)
11
Ground Fault Prot. #1
(See Note 2 Below)
C1
0 VAC (Fault)
24 VAC (No Fault)
12
Ground Fault Prot. #2
(See Note 2 Below)
C2
0 VAC (Fault)
24 VAC (No Fault)
13
Remote Start/Stop
UT
0 VAC (Disable)
24 VAC (Enable)
14 Open
15
Mechanical High Pressure/Motor Protect
Circuit 1
C2
0 VAC (Fault)
24 VAC (No Fault)
16
Mechanical High Pressure/Motor Protect
Circuit 2
C2
0 VAC (Fault)
24 VAC (No Fault)
17
Ice Mode Switch
UT
0 VAC (Cool)
24 VAC (Ice)
18 Open
NOTES:
1.
See Safety Alarms Table for “Phase Voltage Protection”. Units with single point electrical connection
will have one PVM with Inputs 9 and 10 wired together. Units with multiple point connection will
have two PVM’s with Input 9 for Electrical Circuit #1 and Input 10 for Electrical Circuit #2.
2. See Safety Alarms Table 40 for “Ground Fault Protection”. Units with single point electrical
connection will have one GFP with Inputs 11 and 12 wired together. Units with multiple point
connection will have two GFP’s with Input 11 for Electrical Circuit #1 and Input 12 for Electrical
Circuit #2.
Table 38, Digital Outputs
No. Description
Type Load Output
OFF
Output
ON
1
Alarm
C1,C2,UT
Alarm Indicator
Alarm OFF
Alarm ON
2
Evaporator Water Pump
UT
Pump Contactor
Pump OFF
Pump ON
3
Condenser Fan #1
C1
Fan Contactor
Fan OFF
Fan ON
4
Motor Control Relay #1 =
Compr#1
C1 Starter
Compressor
OFF
Compressor
ON
5
Motor Control Relay #3 =
Compr#3
C1 Starter
Compressor
OFF
Compressor
ON
6
Motor Control Relay #5 =
Compr#5
C1 Starter
Compressor
OFF
Compressor
ON
7
Liquid Line #1
C1
Solenoid
Cooling OFF
Cooling ON
8
Condenser Fan #2
C2
Fan Contactor
Fan OFF
Fan ON
9
Motor Control Relay #2 =
Compr#2
C2 Starter
Compressor
OFF
Compressor
ON
10
Motor Control Relay #4 =
Compr#4
C2 Starter
Compressor
OFF
Compressor
ON
11
Motor Control Relay #6 =
Compr#6
C2 Starter
Compressor
OFF
Compressor
ON
12
Liquid Line #2
C2
Solenoid
Cooling OFF
Cooling ON
13
Condenser Fan #3
C1
Fan Contactor
Fan OFF
Fan ON
14
Hot Gas Bypass #1
C1
Solenoid
Cooling OFF
Cooling ON
15
Hot Gas Bypass #2
C2
Solenoid
Cooling OFF
Cooling ON
16
Condenser Fan #4
C2
Fan Contactor
Fan OFF
Fan ON
17
Condenser Fan #5 ( on 8
Fans Only)
C1
Fan Contactor
Fan OFF
Fan ON
18
Condenser Fan #6 ( on 8
Fans Only)
C2
Fan Contactor
Fan OFF
Fan ON