IOMM AGZ-5
AGZ 026B through 130B
73
VFD Monthly and Yearly Inspection Chart
Frequency
Item Inspected
Check for ...
Month
Year
Inspection Method
Criteria
Ambient
environment
Extreme Temperatures &
humidity
Thermometer,
hygrometer
Ambient temperature
between – 10 to 40°C, non-
condensing
Major devices
Abnormal noise &
vibration
Visual & aural
Stable environment for
electronic controls
Overall
Power supply
voltage
Voltage tolerance
Digital volt meter, measure
between inverter terminals
[L1], [L2], [L3}
200V class:
200 to 240V 50/60 Hz
400V class:
380 to 460V 50/60 Hz
Ground Insulation
Adequate resistance
Digital volt meter, GND to
terminals
5 Meg. Ohms or greater
Mounting
No loose screws
Torque wrench
M3: 0.5 – 0.6 Nm
M4: 0.98 – 1.3 Nm
M5: 1.5 – 2.0 Nm
Components Overheating
Thermal trip events
No trip events
Housing Dirt,
dust
Visual
Vacuum dust & dirt
Terminal block
Secure connections
Visual No
abnormalities
Smoothing
capacitor
Leading, swelling
Visual
No abnormalities
Relay(s) Chattering
Aural
Single click when switching
ON or OFF
Resistors
Cracks or discoloring
Visual
Use Ohm meter to check
braking resistors
Noise
Power down, manually rotate
Rotation must be smooth
Main
circuit
Cooling fan
Dust
Visual
Vacuum to clean
Overall
No order, discoloring,
corrosion
Visual No
abnormalities
Control
circuit
Capacitor
No leaks or deformation
Visual
Undistorted
appearance
Display LEDs
Legibility
Visual
All LED segments work