IOMM AGZ-5
AGZ 026B through 130B
43
Electrical Data - High Ambient
Table 29, AGZ 026BB/BH – 070BB/BH, Electrical Data, Single Point
Power Supply
Field Wire
AGZ Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Quantity
Wire
Gauge
75C
Recomm’d.
Fuse
Or HACR
Breaker
Size
Max. Fuse
Or HACR
Breaker
Size
208
147
3
1/0
175
175
230
133
3
1/0
150
150
380
80
3
#4
90
90
460
68
3
#4
80
80
026B
575
53
3
#6
60
60
208
158
3
2/0
175
175
230
144
3
1/0
175
175
380
88
3
#3
100
100
460
74
3
#4
90
90
030B
575
59
3
#6
70
70
208
168
3
2/0
200
200
230
155
3
2/0
175
175
380
96
3
#3
110
110
460
80
3
#4
90
90
035B
575
64
3
#6
70
70
208
187
3
3/0
200
200
230
167
3
2/0
200
200
380
113
3
#2
125
125
460
84
3
#4
90
90
040B
575
70
3
#4
80
80
208
207
3
4/0
225
225
230
188
3
3/0
225
225
380
123
3
#1
125
125
460
94
3
#3
110
110
045B
575
78
3
#4
90
90
208
226
3
4/0
225
225
230
207
3
3/0
225
225
380
132
3
1/0
150
150
460
104
3
#2
125
125
050B
575
86
3
#3
100
100
208
249
3
250
250
250
230
229
3
4/0
250
250
380
147
3
1/0
175
175
460
115
3
#2
125
125
055B
575
96
3
#3
110
110
208
270
3
300
300
300
230
248
3
250
250
250
380
160
3
2/0
175
175
460
124
3
#1
150
150
060B
575
105
3
#2
125
125
208
303
3
350
350
350
230
282
3
300
350
350
380
164
3
2/0
200
200
460
138
3
1/0
175
175
065B
575
115
3
#2
125
125
208
323
3
400
400
400
230
304
3
350
350
350
380
172
3
2/0
200
200
460
150
3
1/0
175
175
070B
575
123
3
#1
150
150
NOTES:
1.
Units operating in ambient temperatures above 95°F (35°C) must use the Maximum Fuse or
HACR Breaker size.
2.
All Electrical Data notes are on page 49.
3.
Conduit hubs are not provided.