IOMM AGZ-5
AGZ 026B through 130B
27
Phase Loss/Voltage Protection
Phase loss with under/over voltage protection and multiple LED indication of fault
type is available as a factory-installed option to guard against compressor motor
burnout.
Convenience Outlet
10.0 amp, 115-volt outlet located in control panel to provide power for servicing unit.
Ground Fault Protection
Protects equipment from damage from line-to-ground fault currents less than those
required for conductor protection.
High Short Circuit Current Protection
Provides control panel protection against short circuit currents per the following table:
Voltage 208
240
460
600
Current (kA)
120
100
65
25
High Ambient Control Panel
Consists of exhaust fan with rain hood, two inlet screens with filters, necessary
controls and wiring to allow operation to 125
°
F. The option can be factory or field
installed as a kit. Must be used for:
•
Ambient temperatures above 105
°
F (40
°
C) with fan VFD (low ambient option)
•
Ambient temperatures above 115
°
F (46
°
C) with standard FanTrol control.