One caution point we need to take care with parallel pumping of different pump capacities is to
ensure the operating head pressure does not cause the pump of lower capacity to operate at
shut-off conditions and cause over-heating, i.e. at point X.
Therefore, it is very important to have a thorough understanding of the operating condition when
operating parallel pumps. Always check with the pump curves.
Pumps may also operate together in
series
. This is done to increase the head pressure for a
particular flowrate. However, it is not recommended for the mini chiller units to be installed in
series. This will cause problems in controlling the water temperature and may cause damage to
the heat exchangers and pumps.
Should the need arises, install the pump along the water discharge line to boost the head
pressure.
Example: The head pressure of the pump in chiller C1 is not sufficient to overcome the total
friction loss to the the load. Therefore, an additional pump P1 is installed to increase the
head pressure at the same water flowrate, Q, from HP1 to HP2.
C1
LOAD
P1
LOAD
C1
The pump curve will look as follows:
Head pressure
combined pump curve with the
head pressures added together for
HP2
C1 and P1
pump curve of chiller C1
HP1
pump
curve
of
P1
Flowrate
Q
Section 5
Page 81
Summary of Contents for AC 40A
Page 1: ...AM MAC ...
Page 153: ...Appendix 1 ...
Page 154: ...Appendix 2 Appendix 2 ...
Page 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Page 158: ......
Page 159: ...Water Capacity Graph Appendix 5 2 ...
Page 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Page 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Page 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Page 168: ...Appendix 8 Appendix 8 ...
Page 169: ...Appendix 8 1 ...
Page 170: ...Appendix 8 2 ...
Page 171: ...Appendix 8 3 ...
Page 172: ...Appendix 8 4 ...
Page 173: ...Appendix 8 5 Appendix 8 5 ...
Page 174: ...Appendix 8 6 Appendix 8 6 ...
Page 175: ...Appendix 8 7 Appendix 8 7 ...
Page 176: ...Appendix 9 ...
Page 178: ...Appendix 11 1 Appendix 11 1 ...
Page 179: ...Appendix 11 2 Appendix 11 2 ...
Page 180: ...Appendix 13 ...
Page 181: ...Appendix 13 1 ...
Page 182: ...Appendix 14 Appendix 14 ...
Page 183: ...Appendix 15 1 Appendix 15 1 ...
Page 186: ...Appendix 17 Appendix 17 ...
Page 187: ...Appendix 18 ...
Page 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Page 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...