Such brackets must have sufficient strength to carry the weight of the chiller unit. It is
recommended that angle bars (e.g. 38mm*38mm*3mm
t
) or hollow section bars (e.g. 25mm*
50m*2mm
t
) to be used for fabricating these brackets.
These brackets must also allow clearance for removal of service panels for maintenance
purposes.
In any case, it is vital that the chiller unit is secured firmly onto the concrete floor/slab or steel
bracket by using studs, wall plugs or bolts/nuts at the four (4) mounting holes located at the base
plate of the chiller. The weight of the chiller unit and the water pipe connections are not sufficient
to prevent unit movement should any sudden impact or strong vibrations occur in the unit. Failure
to do so may cause the water pipes to deform and break.
It is further recommended that rubber isolation pads (1/2" thick) to be placed beneath each
mounting hole to prevent excessive vibration and noise. If necessary, isolating springs can
also be mounted.
The following pages are examples of these isolation pads and springs.
Section 1
Page 5
Summary of Contents for AC 40A
Page 1: ...AM MAC ...
Page 153: ...Appendix 1 ...
Page 154: ...Appendix 2 Appendix 2 ...
Page 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Page 158: ......
Page 159: ...Water Capacity Graph Appendix 5 2 ...
Page 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Page 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Page 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Page 168: ...Appendix 8 Appendix 8 ...
Page 169: ...Appendix 8 1 ...
Page 170: ...Appendix 8 2 ...
Page 171: ...Appendix 8 3 ...
Page 172: ...Appendix 8 4 ...
Page 173: ...Appendix 8 5 Appendix 8 5 ...
Page 174: ...Appendix 8 6 Appendix 8 6 ...
Page 175: ...Appendix 8 7 Appendix 8 7 ...
Page 176: ...Appendix 9 ...
Page 178: ...Appendix 11 1 Appendix 11 1 ...
Page 179: ...Appendix 11 2 Appendix 11 2 ...
Page 180: ...Appendix 13 ...
Page 181: ...Appendix 13 1 ...
Page 182: ...Appendix 14 Appendix 14 ...
Page 183: ...Appendix 15 1 Appendix 15 1 ...
Page 186: ...Appendix 17 Appendix 17 ...
Page 187: ...Appendix 18 ...
Page 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Page 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...