Reworking the example by using the lower temperature as 0°C and the higher
temperature as 80°C, we will get:
[ ]
(0.001028/0.001) - 1] - (3*11.7*10
-6
)(80-0)
1 - (80/300)
V
t
= 125
= 4.29 litres
(5.1 litres with 20% safety factor)
Thus, a 6 litres tank is needed.
Therefore, the higher the water temperature, the larger the volume of the tank that
is required.
Note:
If the tank is located at a location with lower pressure, it can be seen that the
volume required will be smaller. Therefore, the expansion tank should be located
at the position with the a low pressure, e.g. on the water return suction line or at the
highest point of a vertical pipe system.
To calculate the expansion tank size for cooling only systems, use the lower temperature as
the design chilled water temperature and the higher temperature as the ambient
temperature (e.g. 35°C).
Generally, the size of the expansion tank for chilled water system is much smaller compared
with the hot water applications.
Using a larger expansion tank than the calculate requirement is OK. The larger volume
will not affect the system, rather it will help to cater for a larger water volume than the value
used in the calculation.
An expansion tank is not required for an open piping system as the reservoir tank itself
will allow for the expansion.
There should only be ONE expansion tank in the close piping system.
Section 6
Page 92
Summary of Contents for AC 40A
Page 1: ...AM MAC ...
Page 153: ...Appendix 1 ...
Page 154: ...Appendix 2 Appendix 2 ...
Page 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Page 158: ......
Page 159: ...Water Capacity Graph Appendix 5 2 ...
Page 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Page 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Page 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Page 168: ...Appendix 8 Appendix 8 ...
Page 169: ...Appendix 8 1 ...
Page 170: ...Appendix 8 2 ...
Page 171: ...Appendix 8 3 ...
Page 172: ...Appendix 8 4 ...
Page 173: ...Appendix 8 5 Appendix 8 5 ...
Page 174: ...Appendix 8 6 Appendix 8 6 ...
Page 175: ...Appendix 8 7 Appendix 8 7 ...
Page 176: ...Appendix 9 ...
Page 178: ...Appendix 11 1 Appendix 11 1 ...
Page 179: ...Appendix 11 2 Appendix 11 2 ...
Page 180: ...Appendix 13 ...
Page 181: ...Appendix 13 1 ...
Page 182: ...Appendix 14 Appendix 14 ...
Page 183: ...Appendix 15 1 Appendix 15 1 ...
Page 186: ...Appendix 17 Appendix 17 ...
Page 187: ...Appendix 18 ...
Page 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Page 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...