Close System vs. Open System
The mini chiller has been designed with an application for a close water piping system.
However, it is still possible to use the unit with an open system by means of an additional
buffer tank.
In such a system, the chiller will discharge the chilled water into the tank while a secondary
external pump will then pump the water to the fan coil units.
It is recommended that the tank to have a baffle plate in between to isolate the two return
water from the chiller and fan coil load. This will prevent the hotter return water temperature
from the load mixing with the cold chilled water from the chiller.
Such a method is suitable for:
-
multiple chillers operation
-
multiple secondary pumps supplying chilled water to several zones
The water volume in the tank can also be sized to act as a storage to provide cold water to the fan
coil units. By doing so, the chiller may be cycled-off for longer periods of time, hence saving energy
costs.
However, since this is an open system, there is a higher chance of air entering the water.
Care must also be taken to ensure there are no leakages along the pump suction line else
air will enter the system. The air will be drawn into the buffer tank and accumulate there. This
may affect the water flow rate and trip the chiller unit. Always ensure the automatic air vent
on the buffer tank is operating properly to release any trapped air.
Supply to load
Return from load
Tank
Chiller Secondary
pump
Check if this air
vent is OK or not!!
Buffer tank
*** See Page 25 for more information
Section 2
Page 14
Summary of Contents for AC 40A
Page 1: ...AM MAC ...
Page 153: ...Appendix 1 ...
Page 154: ...Appendix 2 Appendix 2 ...
Page 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Page 158: ......
Page 159: ...Water Capacity Graph Appendix 5 2 ...
Page 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Page 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Page 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Page 168: ...Appendix 8 Appendix 8 ...
Page 169: ...Appendix 8 1 ...
Page 170: ...Appendix 8 2 ...
Page 171: ...Appendix 8 3 ...
Page 172: ...Appendix 8 4 ...
Page 173: ...Appendix 8 5 Appendix 8 5 ...
Page 174: ...Appendix 8 6 Appendix 8 6 ...
Page 175: ...Appendix 8 7 Appendix 8 7 ...
Page 176: ...Appendix 9 ...
Page 178: ...Appendix 11 1 Appendix 11 1 ...
Page 179: ...Appendix 11 2 Appendix 11 2 ...
Page 180: ...Appendix 13 ...
Page 181: ...Appendix 13 1 ...
Page 182: ...Appendix 14 Appendix 14 ...
Page 183: ...Appendix 15 1 Appendix 15 1 ...
Page 186: ...Appendix 17 Appendix 17 ...
Page 187: ...Appendix 18 ...
Page 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Page 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...