Section 12: Flow Switch
The function of the flow switch is to switch off the chiller unit when a low water flow rate
condition is detected in the piping. Such occurances may happen due to:
1.
pump
failure
2.
blocked
BPHE
3. accidental closing of shut-off valves
4.
failure
of
control
valves
This protection against low water flow rate is necessary to prevent the water from freezing in the
BPHE. Ice formation in between the plates in the BPHE will cause cracking.
The mini chiller has a flow switch installed in the piping, at the following location:
Water out
Water in
BPHE
Flow switch
The flow switch used in the chiller is JOHNSON CONTROLS model F61KB or F61SB.
##
However, for field replacements, other brands of equivalent sizes may be used.
The flow switch is of the paddle type whereby the switch is connected mechanically to a length of
stainless steel paddles which the water flow will impact upon. As a result, the paddle will move in
the flow direction and thus closes the electrical contact.
The length of the paddles can be adjusted by selecting the number of segments to use. The
paddles can also be trimmed with a pair of scissors to suit requirement.
Note ##
Or equivalent;
Flow switch
used only in A and B series
chillers.
paddle segments
Flow
Section 12
Page 141
Summary of Contents for AC 40A
Page 1: ...AM MAC ...
Page 153: ...Appendix 1 ...
Page 154: ...Appendix 2 Appendix 2 ...
Page 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Page 158: ......
Page 159: ...Water Capacity Graph Appendix 5 2 ...
Page 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Page 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Page 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Page 168: ...Appendix 8 Appendix 8 ...
Page 169: ...Appendix 8 1 ...
Page 170: ...Appendix 8 2 ...
Page 171: ...Appendix 8 3 ...
Page 172: ...Appendix 8 4 ...
Page 173: ...Appendix 8 5 Appendix 8 5 ...
Page 174: ...Appendix 8 6 Appendix 8 6 ...
Page 175: ...Appendix 8 7 Appendix 8 7 ...
Page 176: ...Appendix 9 ...
Page 178: ...Appendix 11 1 Appendix 11 1 ...
Page 179: ...Appendix 11 2 Appendix 11 2 ...
Page 180: ...Appendix 13 ...
Page 181: ...Appendix 13 1 ...
Page 182: ...Appendix 14 Appendix 14 ...
Page 183: ...Appendix 15 1 Appendix 15 1 ...
Page 186: ...Appendix 17 Appendix 17 ...
Page 187: ...Appendix 18 ...
Page 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Page 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...