2. For close systems, use the following equation:
NPSHA = P
a
+ P
s
+ (v
2
/2g) - P
vp
where P
a
is the atmospheric pressure
P
s
is the pressure at the pump inlet
v
is the velocity of water at the pump inlet
g
is the accelaration due to graviti (32.17 ft/sec
2
or 9.81 m/sec
2
)
P
vp
is the vapour pressure of water at the operating temperature
[Note: The term v
2
/2g is the velocity head of water at the pump inlet]
For both equations 1 and 2, it is recommended that an additional of 2 m (6.56 ft) to be
deducted from the NPSHA as a safety factor to cater for the actual pipe installation.
Example 1:
A mini chiller (C1) is installed with a storage tank in the following configuration:
Return water
Storage tank (7°C)
H = 6ft.
Supply water
C1
The chiller operate at the following parameters: Flowrate = 8 USGPM (1.82 m
3
/hr);
the total suction line friction losses = 2 ft; the internal friction loss from the chiller
inlet pipe to the pump inlet = 1.6 ft.
The water tank is elevated at a height of 6 ft.
The chiller has a water pump of model CH2-30.
At 7°C, the water vapour pressure is 0.34 ft wg.
The atmospheric pressure at the site of installation is 34.0 ft wg.
By using equation 1, we calculate:
NPSHA = 34 + 6 - 0.34 - (2+1.6) = 36 ft.
By taking a safety factor of 6.56 ft, we get NPSHA = 29.44 ft.
Section 5
Page 83
Summary of Contents for AC 40A
Page 1: ...AM MAC ...
Page 153: ...Appendix 1 ...
Page 154: ...Appendix 2 Appendix 2 ...
Page 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Page 158: ......
Page 159: ...Water Capacity Graph Appendix 5 2 ...
Page 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Page 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Page 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Page 168: ...Appendix 8 Appendix 8 ...
Page 169: ...Appendix 8 1 ...
Page 170: ...Appendix 8 2 ...
Page 171: ...Appendix 8 3 ...
Page 172: ...Appendix 8 4 ...
Page 173: ...Appendix 8 5 Appendix 8 5 ...
Page 174: ...Appendix 8 6 Appendix 8 6 ...
Page 175: ...Appendix 8 7 Appendix 8 7 ...
Page 176: ...Appendix 9 ...
Page 178: ...Appendix 11 1 Appendix 11 1 ...
Page 179: ...Appendix 11 2 Appendix 11 2 ...
Page 180: ...Appendix 13 ...
Page 181: ...Appendix 13 1 ...
Page 182: ...Appendix 14 Appendix 14 ...
Page 183: ...Appendix 15 1 Appendix 15 1 ...
Page 186: ...Appendix 17 Appendix 17 ...
Page 187: ...Appendix 18 ...
Page 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Page 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...