Capacity Control With 2-Way and 3-Way Valves
supply return supply ret
urn
The load of the fan coil unit can be calculated from the equation:
Q = 4180 * (water flow rate, L/s) * (water temperature differential.°C) Watt
th the 2- ay and 3- ay
alve will vary t
∆
t".
LOAD
LOAD
LOAD
2 way
diverting
mixing
Therefore, the load is propotional to the water flow rate and
∆
t. Bo
w
w
v
he flow rate to accomodate changes in the load demand.
With the 2-way valve, the system is considered as "variable flow, constant
∆
t".
With the 3-way valve, the system is considered as "constant flow, variable
It is recommended that the 3-way valve to be configured as a diverting valve instead of a mixing
valve. This is because when the fan coil unit is OFF, cold water will not enter into the heat
exchanger with the valve diverting the water away to the return line. Unlike the mixing valve, even
though the valve may be closed, cold water can still enter into the heat exchanger and ccumulate
there. As a result, sweating
on the heat exchanger and the connecting joints will occur even
the fan coil unit is not running.
However, on the o
when
ch valves, choosing instead the mixing configuration.
ther hand, 3-way diverting valves cost more than mixing valves. This is why
some designs do not call for su
Section 3
Page 48
Summary of Contents for AC 40A
Page 1: ...AM MAC ...
Page 153: ...Appendix 1 ...
Page 154: ...Appendix 2 Appendix 2 ...
Page 157: ...GRAPH OF PRESSURE DROP VS FLOW FOR VARIOUS C V RATINGS Appendix 5 1 ...
Page 158: ......
Page 159: ...Water Capacity Graph Appendix 5 2 ...
Page 160: ...CHART 3 FRICTION LOSS FOR CLOSED PIPING SYSTEMS Appendix 6 1 ...
Page 161: ...CHART 4 FRICTION LOSS FOR OPEN PIPING SYSTEMS Appendix 6 2 ...
Page 162: ...CHART 5 FRICTION LOSS FOR CLOSED AND OPEN PIPING SYSTEMS Appendix 6 3 ...
Page 168: ...Appendix 8 Appendix 8 ...
Page 169: ...Appendix 8 1 ...
Page 170: ...Appendix 8 2 ...
Page 171: ...Appendix 8 3 ...
Page 172: ...Appendix 8 4 ...
Page 173: ...Appendix 8 5 Appendix 8 5 ...
Page 174: ...Appendix 8 6 Appendix 8 6 ...
Page 175: ...Appendix 8 7 Appendix 8 7 ...
Page 176: ...Appendix 9 ...
Page 178: ...Appendix 11 1 Appendix 11 1 ...
Page 179: ...Appendix 11 2 Appendix 11 2 ...
Page 180: ...Appendix 13 ...
Page 181: ...Appendix 13 1 ...
Page 182: ...Appendix 14 Appendix 14 ...
Page 183: ...Appendix 15 1 Appendix 15 1 ...
Page 186: ...Appendix 17 Appendix 17 ...
Page 187: ...Appendix 18 ...
Page 188: ...CE20DW CE25DW Note PRESSURE DROP CORRECTION FACTOR 1 2947 0 0021 EWTºF Appendix 19 ...
Page 189: ... 2003 McQuay International 603 55194922 www mcquayup com ISO 9002 REGISTERED ...