CAN Connector (J7, J8)
Connection of Positioning Controller to CAN Bus Line CiA DS-102
Note
• Consider CAN devices’ maximal baud rate.
• The standard baud rate setting (factory setting) is 1 MBit/s.
• Use termination resistor at both ends of the CAN bus (
chapter “4.8.2 CAN Bus Termination in
• CAN-S (J7) is used for a CAN Slaves Network.
• CAN-M (J8) is used for a Supervisor Control (Master) Network.
• For detailed CAN information
separate document «EPOS2 Communication Guide».
Figure 4-30
CAN Connector (J7/J8)
Standard
ISO 11898-2:2003
Max. bit rate
1 Mbit/s
Max. number of CAN nodes
127
Protocol
CANopen DS-301
Identifier setting
DIP switch or software
EPOS2 P 24/5
CAN 9 pin D-Sub (DIN41652)
Connector [J7] or [J8] Pin [1] “CAN high”
Pin 7 “CAN_H” high bus line
Connector [J7] or [J8] Pin [2] “CAN low”
Pin 2 “CAN_L” low bus line”
Connector [J7] or [J8] Pin [3] “CAN GND”
Pin 3 “CAN_GND” Ground
Connector [J7] or [J8] Pin [4] “CAN shield”
Pin 5 “CAN_Shield” cable shield
Pin
Signal
Description
1
CAN high
CAN high bus line
2
CAN low
CAN low bus line
3
CAN GND
CAN Ground
4
CAN shield
Cable shield
Accessories
Cables
CAN-COM Cable (275908)
CAN-CAN Cable (275926)
CAN-Y Cable (319471)
Notes
Suitable connector
Suitable crimp terminals
Suitable hand crimper
Molex Micro-Fit 3.0 4 poles (430-25-0400)
Molex Micro-Fit 3.0 female crimp terminals (43030-xxxx)
Molex hand crimper (63819-0000)