Lucent Technologies Lineage
®
2000 125A Ferroresonant Rectifier J85502C-1
5 - 8 Installation
Issue 8 July 1999
Unpacking
Move the crated rectifier to a convenient area for uncrating and
follow the steps listed below.
1. Remove any shipping bands.
2. Check “tilt” or “shock” indicators. If tripped, contact
shipping company and process claims form.
3. Pry off top, then sides of crate.
4. Inspect exposed exterior of rectifier for shipping damage.
5. With rectifier lying on its back, open the front door and
visually inspect for shipping damage.
6. If material is damaged, contact shipping company and
process claims form.
7. Verify that the main ac voltage at the distribution panel
agrees with the List options specified on the label inside
the front door of the rectifier. If it does not agree, two
possible conditions on the rectifier may be corrected by the
customer:
–
Incorrect ac input voltage (see Table 3-A)
–
Incorrect system polarity (circuit breaker in the wrong
dc output bus). Positive ground systems have the
breaker in the negative output bus, and negative ground
systems have the breaker in the positive output bus.
The customer may decide to correct either type of
condition instead of returning the rectifier. The procedure
for rewiring the ac input connections to match the
customer’s ac supply (208 or 240 volts) is provided in
“Converting AC Voltage.” The procedure for placing the
DC OUTPUT circuit breaker (CBA1) in the opposite
output bus is provided in “Converting DC Output
Polarity.”
8. Verify that the CM1 option board has straps present or
removed according to the options you expect. See Table 8-B
in this manual or Tables A and R on J85502C-1 drawing.