Lucent Technologies Lineage
®
2000 125A Ferroresonant Rectifier J85502C-1
8 - 4 Spare Parts and Replacement Procedures
Issue 8 July 1999
•
When soldering static-sensitive semiconductor devices, the
soldering iron must be grounded to the work table which
must also be earth grounded.
•
Do not wax the equipment aisles in central offices.
•
Whenever possible, maintain relative humidity above the
20-percent level.
Modifying the
CM1 Option
Board
As described in schematic drawings SD-82659-01, replacement
CM1 option boards are supplied with all wire straps and
resistors in place. The same wire straps and resistors that were
removed from the original board must be removed from
replacement boards in order for the rectifier to operate properly.
Table 8-B and Figure 6-2 show the straps and resistors to keep
and to remove from the CM1 board for each option on the
J85502C-1 rectifier. The plug-in type wire straps are removed
completely from a 2-hole jack. The other wire straps shown are
soldered in and are never replaced once they are removed.
Table 8-B: Modifications for the CM1 Option Board
Feature
List/Option
Keep Straps
or Resistors
Marked with
Remove Straps or
Resistors Marked
with
Stamping
Added on
ED-83158-30
24V
1
F, V, Q, ZA
K, N, W, T, M
Mod CA
24V, Ext Reg
1 and WA
F, V, Q
K, N, W, T, M, ZA
Mod CB
24V, Ext HVSD
1 and WB
F, V, M, ZA
K, N, W, T, Q
Mod CC
24V, Ext Reg
and HVSD
1, WA and WB
F, V, M
K, N, W, T, Q, ZA
Mod CD
48V
2
F, W, T, ZA
K, N, V, M
Mod CE
48V, Ext Reg
2 and WA
F, W, T
K, N, V, M, Q, ZA
Mod CF
48V, Ext HVSD
2 and WB
F, W, M, ZA
K, N, V, T, Q
Mod CG
48V, Ext Reg
and HVSD
2, WA and WB
F, W, M
K, N, V, T, Q, ZA
Mod CH
Note: Remove Straps P15 (Option Q) and P16 (Option T) if the rectifier is not equipped with
Options Q and T.