Lucent Technologies Lineage
®
2000 125A Ferroresonant Rectifier J85502C-1
Issue 8 July 1999
Spare Parts and Replacement Procedures 8 - 11
All removal and replacement procedures are easier to perform on
bay-mounted rectifiers that have been removed from the bay.
Most component removals are straightforward and obvious.
Therefore, these procedures can be used as a guide by qualified
service personnel, rather than as step-by-step procedures. For
example, you may prefer to remove a part not called for in order
to make more room for access to a component being replaced.
Tables 8-D and 8-E provide the reassembly torquing
requirements for the electrical and mechanical connections in
the rectifier. Use these values unless otherwise directed in the
procedures.
Table 8-D: Torque and Minimum Yield Strength for
Mechanical Connections (Using Hex Head Cap Screws)
Cap Screw
Diameter (Inch)
Min. Yield
Strength (PSI)
Torque (Ft-Lb)
UNC
1/4
57,000
6
5/16
57,000
12
3/8
57,000
22
7/16
57,000
35
1/2
57,000
54
9/16
57,000
77
5/8
57,000
107
3/4
57,000
190
7/8
36,000
193
1
36,000
290
1-1/8
36,000
410
1-1/4
36,000
580
1-3/8
36,000
760
1-1/2
36,000
1010