Lucent Technologies Lineage
®
2000 125A Ferroresonant Rectifier J85502C-1
Issue 8 July 1999
Testing 6 - 3
2. Turn Off (down) the rectifier DC OUTPUT circuit
breaker.
3. Disconnect J2A from CM2 by unlatching first, then pulling
the cable connector.
4. Refer to Figure 5-4 and connect the test load between the +
and – output buses marked on the rectifier.
Caution
Support the CM2 control board when disconnecting the cable
leads or damage to the control board may result.
Do NOT disconnect plant control cable connector J2A from
control board CM2 by pulling the cable.