Reading Alarm And Control Set Points
In addition to being able to read existing operating conditions, the factory-set alarm and control set points
can also be prompted and displayed. The operating variables that are monitored have preset alarm set
points for high and low limits. The air / oil heater also has a control function to control air temperature.
The systems control and alarm set point values are listed in the table below.
Factory Default Set point Values
Set Point Variable
US Units
Metric Units
Air Temperature - Control Set-point
120
F
49
C
Air Temperature - High Alarm Set-point
140
F
60
C
Air Temperature - Low Alarm Set-point
100
F
38
C
Air / Oil Heater - High Temperature Cutout Set-point
150
F
66
C
Regulated Air Pressure - High Alarm Set-point
65 PSI
4.48 BAR
Regulated Air Pressure - Low Alarm Set-point
10 PSI
0.69 BAR
Mist Pressure - High Alarm Set-point
30 In. H
2
O
75 m BAR
Mist Pressure - Low Alarm Set-point
10 In. H
2
O
25 m BAR
Mist Density - High Alarm Set-point
90 %
90 %
Mist Density - Low Alarm Set-point
10 %
10 %
Oil Reservoir Level - High Alarm Set-point
80%
80%
Oil Reservoir Level - Low Alarm Set-point
35%
35%
The factory default control and alarm set points for the operating functions listed above can be prompted and
displayed for review. The first step is to identify which function the controller is to display. To view the
variable control and alarm set point values follow these steps:
1. Press the [SET
]
key.
2. Press the variable <FUNCTION> key that is to be viewed.
3. Use the [ENTER] key to toggle through the control-high-low -cutout set point values for each operating
variable. Note that as the set point variables are scrolled, a message is displayed to alert the operator
that set point adjustments are not allowed.
4. After the last set point value is displayed for the specified operating variable, press [ENTER] to return
the screen to normal view.
The controller continues to monitor and control normally while doing set point queries.
To change the factory default control and alarm set point values see
Programming User Established Alarm
And Control Set Points
in the section titled OPERATING GUIDE of this manual.