Connection of detectors Labor Strauss
Chapter 2 • Conventional technology
91
2.14
Coding of Address Module NG58-1
Together with the Fire Detection Control Panels Series BC216 (with a Conventional Detector Interface
GIF8-1), BC016 and BC600 (with a Conventional Detector Interface GIF608-1), the Address Module
NG58-1 allows the exact identification of a detector in alarm condition. The number of the detector in
alarm condition will be displayed on the fire detection control panel. The number to be displayed must
be preset (coded) on the address module within the range 0 to 63.
On the Fire Detection Control Panels Series BC016 and Series BC216, the evaluation of the address
module must be set to
binary
in the parameter setup (menu
Global settings
). In the case of the
BC600 it is not necessary to parameterise the type of evaluation. The Fire Detection Control Panel
Series BC06 does not support address modules.
The number is preset by cutting the corresponding address jumpers. According to their order, the six
jumpers have the following values:
binary coding:
1, 2, 4, 8, 16 and 32
Example: number 25
binary coding:
25 = 16 + 8 + 1 -->
Jumpers with the value 16, 8 and 1 must be cut.
Example: number 12
binary coding:
12 = 8 + 4
-->
Jumpers with the value 8 and 4 must be cut.
Connection-LST.odt / 2009 / AN9161298