24
Chapter 2 • Conventional technology
Connection of detectors Labor Strauss
2.4.2.2 Connection
2.4.2.3 Connection with Diode Base FC600/BRD
The detector base with integrated diode may only be used with a capacitive end-of-line element. At
the moment only the BC06 and the BC600 can fulfil this requirement. The installation of diode bases
with end-of-line resistors is not allowed. In the settings of the control panel, a capacitor must be para-
meterised as an end-of-line element.
Connection-LST.odt / 2009 / AN9161298
200/24