126
Chapter 3 • ADM technology
Connection of detectors Labor Strauss
3.8.5
Flame Detector Series 16000
3.8.5.1 Note
The supply voltage of the flame detector is routed via the Conventional Zone Module FI700/M1CZ.
The supply voltage is interrupted by the module to reset the alarm condition.
By means of the DIP switches, the detector can be adjusted to the various operating conditions. The
switches 6 and 7 allow you to change the response time.
Type
EN 54-10 Class 1
SW6
SW7
Response time
16581
IR2
0
0
8s
16589
IR3
1
0
4s
16591
UV/IR2
0
1
2s
1
1
1s
3.8.5.2 Connection
If the conventional zone module is powered by an external power supply, the country-specific regula-
tions concerning emergency power supply have to be observed.
Connection-LST.odt / 2009 / AN9161298
200/126
126